HYDAC ELECTRONIC EDS 3000 Operating Instructions Manual

HYDAC ELECTRONIC EDS 3000 Operating Instructions Manual

Electronic pressure switch with io-link interface
Table of Contents

Advertisement

Available languages

Available languages

Quick Links

 
 
 
 
 
 
 
 
 
 
Bedienungsanleitung
(Originalanleitung)
Operating Instructions
(Translation of original
instructions)
 
Elektronischer Druckschalter
Electronic Pressure Switch
EDS 3000
Mit IO-Link Schnittstelle
 
With IO-Link Interface

Advertisement

Chapters

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EDS 3000 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for HYDAC ELECTRONIC EDS 3000

  • Page 1     Elektronischer Druckschalter   Electronic Pressure Switch     EDS 3000     Mit IO-Link Schnittstelle   With IO-Link Interface         Bedienungsanleitung (Originalanleitung) Operating Instructions (Translation of original instructions)
  • Page 2: Table Of Contents

    4.4 Personalauswahl und Qualifikation; Grundsätzliche Pflichten 4.5 Organisatorische Maßnahmen Transport, Verpackung, Lagerung 5.1 Transport 5.2 Verpackung 5.3 Lagerung Entsorgung Funktionen des EDS 3000 Wartung und Instandhaltung Montage 9.1 Allgemeine Montagehinweise 9.2 Zusätzliche Montagehinweise Bedienelemente des EDS 3000 Betriebsarten 11.1 SIO-Mode 11.2 SDCI-Mode...
  • Page 3 22.1 EDS 3000 mit Keramik-Sensorzelle; Absolut- und Relativdruck bis 16 bar (500 psi) 22.2 EDS 3000 mit Dünnfilm-DMS-Sensorzelle; Relativdruck 22.3 Relevante Daten für IO-Link Typenschlüssel 23.1 EDS 3000 mit Keramik-Sensorzelle; Absolut- und Relativdruck bis 16 bar (500 psi) 23.2 EDS 3000 mit Dünnfilm-DMS-Sensorzelle; Relativdruck Geräteabmessungen Zubehör 25.1 Elektrischer Anschluss 25.2 Mechanischer Anschluss...
  • Page 4 EDS 3000 IO-Link Vorwort Für Sie, den Benutzer unseres Produktes, haben wir in dieser Dokumentation die wichtigsten Hinweise zum Bedienen und Warten zusammengestellt. Sie dient Ihnen dazu, das Produkt kennen zu lernen und seine bestimmungs- gemäßen Einsatzmöglichkeiten optimal zu nutzen.
  • Page 5: Sicherheitshinweis

    EDS 3000 IO-Link Sicherheitshinweis Überprüfen Sie vor der Inbetriebnahme den Zustand des Gerätes sowie des mitgelieferten Zubehörs. Lesen Sie vor der Inbetriebnahme des Gerätes die Bedienanleitung und stellen Sie sicher, dass das Gerät für Ihre Anwendung geeignet ist. Falsche Handhabung bzw. die Nichteinhaltung von Gebrauchshinweisen oder technischen Angaben kann zu Sach- und / oder Personenschäden führen.
  • Page 6: Bestimmungsgemäßer Gebrauch / Vorhersehbarer Fehlgebrauch

    EDS 3000 IO-Link Das Symbol bezeichnet wichtige Informationen bzw. Merkmale und Anwendungstipps des verwendeten Produkts. Das Symbol bedeutet, dass entsprechende ESD-Schutzmaßnahmen nach DIN EN 100 015-1 zu beachten sind. (Herbeiführen eines Potentialausgleichs zwischen Körper und Geräte-masse sowie Gehäusemasse über einen hochohmigen Widerstand (ca.
  • Page 7: Organisatorische Maßnahmen

    Person vorgenommen werden. Transport, Verpackung, Lagerung 5.1 Transport Der EDS 3000 wird in einem stabilen Karton verpackt geliefert. Achten Sie bei der Annahme und beim Auspacken auf eventuelle Transportschäden und zeigen Sie diese dem Spediteur unverzüglich an. 5.2 Verpackung Entfernen Sie die Verpackung erst unmittelbar vor der Montage.
  • Page 8: Funktionen Des Eds 3000

     Schalten der Schaltausgänge entsprechend dem Druck und den eingestellten Schaltparametern  Analogausgang Wartung und Instandhaltung Alle Mess-Systeme der Baureihe EDS 3000 sind wartungsfrei. Falls trotzdem Fehler auftreten wenden Sie sich bitte an die HYDAC Systems & Services GmbH. Montage 9.1 Allgemeine Montagehinweise Der elektronische Druckschalter EDS 3000 kann über den Druckanschluss direkt oder...
  • Page 9: Zusätzliche Montagehinweise

    Bei Anschluss an Class B Ports nur 3-adrige Leitung mit PIN 1, 3 und 4 Belegung verwenden Bei Konfiguration von Pin 2 als zusätzlichem Analogausgang darf dieser grundsätzlich nicht mit dem Master verbunden werden. Bedienelemente des EDS 3000 Anzeige der Druckeinheit 4-stellige Digitalanzeige LED-Anzeige für...
  • Page 10: Betriebsarten

    Nach dem Start befindet sich der Druckschalter im SIO-Mode (Standard IO-Mode). In diesem Modus hat Pin 4 die Funktion eines Schaltausganges.  Die Mittel-LED leuchtet dauerhaft. Gemäß Kapitel 15 Grundeinstellungen kann das Verhalten des EDS 3000 an die jeweilige Applikation angepasst werden. 11.2 SDCI-Mode Über einen angeschlossenen IO-Link-Master kann der Druckschalter per Wake-Up-...
  • Page 11: Parametrierung

    Das Zip-file enthält zusätzlich eine pdf-Datei mit einer IODD-Beschreibung. 12.3 Parametrierung im SIO Mode Wird IO-Link nicht genutzt, so arbeitet der EDS 3000 IO-Link als Druckschalter mit 2 Schaltausgängen oder 1 Schaltausgang und 1 Analogausgang. Er kann mittels der integrierten Bedienknöpfe (Menüführung siehe Kapitel 15 Grundeinstellungen), mit dem HYDAC Programmiergerät HPG P1-000 oder dem...
  • Page 12: Parametrierung Mit Zbe P1-000

    EDS 3000 IO-Link 12.5 Parametrierung mit ZBE P1-000 (Anschluss mit Standardkabel) Q2 / QA ZBE P1 Device Q1 / C Darstellung der Digitalanzeige Darstellung Bezeichnung 7-Segment- Darstellung ASCII Anzeige SP 1 Schaltpunkt, Ausgang 1 RP 1 Rückschaltpunkt, Ausgang 1 Schaltpunkt, Ausgang 2 Rückschaltpunkt, Ausgang 2...
  • Page 13 EDS 3000 IO-Link Darstellung Bezeichnung 7-Segment- Darstellung ASCII Anzeige UN , Einheitenumschaltung Einheit bar Einheit MPa PS , Einheit psi Max-Wert Fehleranzeige D ,S Display Rücksetzen Nein RS.XL Reset Max-Wert rS.HL Programmiersperre Tasten verriegelt FREE Tasten entriegelt Free CAL, Nullpunktkalibrierung...
  • Page 14: Ausgangsverhalten

    EDS 3000 IO-Link Ausgangsverhalten 14.1 Schaltausgänge Der EDS 3000 IO-Link verfügt über 2 Schaltausgänge, deren Schaltverhalten (Window- Mode oder Two-Point-Mode) parametriert werden können. HINWEIS: Wird der Sensor am Class-B-Port eines IO-Link-Master betrieben, darf der Pin 2 des Sensors nicht zu Pin 2 des Masters durchverbunden sein, da dieser hier eine Stromquelle für Geräte mit erhöhtem Strombedarf bzw.
  • Page 15: Window-Mode - Einstellung Auf Fensterfunktion (Fno / Fnc)

    EDS 3000 IO-Link HINWEIS: Eine Einstellung des Schaltpunktes (SP) ist nur möglich, wenn er oberhalb des zugehörigen Rückschaltpunktes (RP) liegt. 14.1.2 Window-Mode - Einstellung auf Fensterfunktion (Fno / Fnc) Die Fensterfunktion ermöglicht es, einen Bereich zu überwachen. Zu jedem Schalt- ausgang können jeweils ein oberer und ein unterer Schaltwert eingegeben werden, die...
  • Page 16: Einstellbereiche Für Die Schaltausgänge

    EDS 3000 IO-Link 14.2 Einstellbereiche für die Schaltausgänge Messbereich Untere Grenze Obere Grenze Mindestabstand Schrittweite* von RP / FL von SP / FH zw. RP und SP bzw. FL und FH in bar in bar in bar in bar - 1 .. 1...
  • Page 17: Grundeinstellungen

    EDS 3000 IO-Link Grundeinstellungen Zur Anpassung an die jeweilige Applikation kann das Verhalten des EDS 3000 über mehrere Einstellungen verändert werden. Diese sind einem Menü zusammengefasst. 15.1 Hauptmenü Der Bereich wird nicht angezeigt, wenn in „Erweiterte Funktionen“ unter „ou2“ „i“ oder „u“ eingestellt ist.
  • Page 18: Erweiterte Funktionen

    EDS 3000 IO-Link 15.2 Erweiterte Funktionen Der Bereich wird nicht angezeigt, wenn in „Erweiterte Funktionen“ unter „ou2“ „i“ oder „u“ eingestellt ist. Stand: 14-07-2022 HYDAC ELECTRONIC GMBH Mat. Nr.: 669897...
  • Page 19: Ändern Der Grundeinstellungen

    EDS 3000 IO-Link Ändern der Grundeinstellungen HINWEIS Erfolgt ca. 60 Sekunden lang keine Tastenbetätigung, wird das Menü automatisch beendet, ohne dass eventuelle Änderungen wirksam werden. Rücksetzen des Spitzenwertes Der Spitzenwert des Druckes kann zurückgesetzt werden.  In den Erweiterten Funktionen die Taste "" betätigen bis der Menüpunkt „rSHL“...
  • Page 20: Programmierfreigabe

    EDS 3000 IO-Link Programmierfreigabe 18.1 Allgemeines Das Gerät verfügt über eine Programmierfreigabe, die erteilt sein muss, um Einstellungen zu ändern. Die Programmierfreigabe kann während des Betriebes gesetzt bzw. aufgehoben werden. Sie bietet Schutz vor unbeabsichtigten Änderungen. 18.2 Ändern der Programmierfreigabe ...
  • Page 21: Fehlermeldungen

    EDS 3000 IO-Link Fehlermeldungen Wird ein Fehler erkannt, so erscheint eine entsprechende Fehlermeldung, die mit einem beliebigen Tastendruck quittiert werden muss. Mögliche Fehlermeldungen sind: E.10 Bei den abgespeicherten Einstellungen wurde ein Datenfehler erkannt. Mögliche Ursachen sind starke elektromagnetische Störungen oder ein Bauteildefekt.
  • Page 22: Anschlussbelegung

    EDS 3000 IO-Link Anschlussbelegung M12x1, 4-polig Q1/C Q2/QA Signal Bezeichnung Q2/QA Schaltausgang (SP2) / Analogausgang Q1/C Schaltausgang (SP1) / IO-Link Kommunikation Stand: 14-07-2022 HYDAC ELECTRONIC GMBH Mat. Nr.: 669897...
  • Page 23: Technische Daten

    EDS 3000 IO-Link Technische Daten 22.1 EDS 3000 mit Keramik-Sensorzelle; Absolut- und Relativdruck bis 16 bar (500 psi) Eingangskenngrößen Keramiksensor Absolutdruck Messbereiche Überlastbereich Berstdruck Keramiksensor Relativdruck -1..1 Messbereiche Überlastbereich Berstdruck Keramiksensor Absolutdruck Messbereiche Überlastbereich Berstdruck Keramiksensor Relativdruck -14,5 bis Messbereiche Überlastbereich...
  • Page 24 EDS 3000 IO-Link Umgebungsbedingungen Kompensierter Temperaturbereich -10 .. +70 °C [-14 .. +158º F] Betriebstemperaturbereich -25 .. +80 °C [-13 .. +176º F] (-25 .. +60 °C für UL-Spezifikation) Lagertemperaturbereich -40 .. +80 °C [-40 .. +176º F] Mediumstemperaturbereich -25 .. +80 °C [-13 .. +176º F ]...
  • Page 25: Eds 3000 Mit Dünnfilm-Dms-Sensorzelle; Relativdruck

    EDS 3000 IO-Link 22.2 EDS 3000 mit Dünnfilm-DMS-Sensorzelle; Relativdruck Eingangskenngrößen Messbereiche -1 .. 1 1000 Überlastbereich 1000 1200 100 100 100 100 125 1250 2000 2000 3000 Berstdruck Messbereiche 1000 3000 6000 9000 Überlastbereich 2900 7250 11600 11600 Berstdruck 1450...
  • Page 26: Relevante Daten Für Io-Link

    EDS 3000 IO-Link Sonstige Größen Versorgungsspannung 9 .. 35 V DC ohne Analogausgang 18 .. 35 V DC mit Analogausgang - limited energy – gemäß 9.3 UL 61010; Class 2; bei Einsatz gemäß UL-Spezifikation UL 1310 / 1585; LPS UL 60950 ...
  • Page 27: Typenschlüssel

    EDS 3000 IO-Link Typenschlüssel 23.1 EDS 3000 mit Keramik-Sensorzelle; Absolut- und Relativdruck bis 16 bar (500 psi) HINWEIS Die Sensoren der Serie EDS 33X6 werden ersetzt durch die Serie EDS 34X6 mit entsprechender Druckstufe. Nachbestellungen für die Sensoren der Serie EDS 33X6 können daher nicht mehr erfolgen.
  • Page 28: Eds 3000 Mit Dünnfilm-Dms-Sensorzelle; Relativdruck

    EDS 3000 IO-Link 23.2 EDS 3000 mit Dünnfilm-DMS-Sensorzelle; Relativdruck EDS 3 4 X 6 - F31 - XXXX - XXX Ausführung (Technologie) = Dünnfilm DMS relativ Anschlussart, mechanisch = G1/2 B DIN EN 837 (nur in Verbindung mit Druckbereich in bar)
  • Page 29: Geräteabmessungen

    EDS 3000 IO-Link Geräteabmessungen Elastomere Profildichtung Stand: 14.07.2022 HYDAC ELECTRONIC GMBH Mat. Nr.: 669897...
  • Page 30: Zubehör

    EDS 3000 IO-Link Zubehör 25.1 Elektrischer Anschluss ZBE 06 (4-pol.) Kupplungsdose M12x1, abgewinkelt Kabeldurchmesser: 3,3 .. 6,6 mm (0.13 .. 0.26 inch) Material-Nr.: 6006788 ZBE 06-02 (4-pol.) Kupplungsdose M12x1, abgewinkelt mit 2 m (78,7 inch) Leitung, Material-Nr.: 6006790 ZBE 06-05 (4-pol.),...
  • Page 31 EDS 3000 IO-Link ZBM 3100 Schelle zur Wandbefestigung, anschweißbar (Werkstoff Schweißlasche: QSTE340TM, galvanischer Überzug EN 12329 FE/ZN8/B; Unterteil: TPE Santoprene 10187; Oberteil: Bandstahl DIN 95381-1.4571) Material-Nr.: 3184632 ZBM 3200 Spritzwasserschutz (Werkstoff: Elastollan S60 A15 SPF 000) Material-Nr.: 3201919 Stand: 14.07.2022 HYDAC ELECTRONIC GMBH Mat.
  • Page 32: Abkürzungsverzeichnis

    EDS 3000 IO-Link Abkürzungsverzeichnis Wert-Fenster oberer Wert Wert-Fenster unterer Wert Fensterfunktion Öffner Fensterfunktion Schließer Full Scale IODD IO Device Description ISDU Indexed Service Data Unit Ausgangsfunktion Rückschaltpunkt SDCI Single-drop digital communication interface Standard IO-Modus Schaltpunkt Schaltsignalkanal Stand: 14-07-2022 HYDAC ELECTRONIC GMBH...
  • Page 33: Kontakt

    EDS 3000 IO-Link Kontakt HYDAC ELECTRONIC GMBH Hauptstr. 27 D-66128 Saarbrücken Germany Web: www.hydac.com E-Mail: electronic@hydac.com Tel.: +49 (0)6897 509-01 Fax.: +49 (0)6897 509-1726 HYDAC Service Für Fragen zu Reparaturen steht Ihnen der HYDAC Service zur Verfügung. HYDAC SYSTEMS & SERVICES GMBH Hauptstr.
  • Page 34 Notizen / Notes / Notes                                                                        ...
  • Page 35 Electronic Pressure Switch EDS 3000 with IO-Link Interface Operating Instructions (Translation of original instructions)
  • Page 36 5.3 Storage Disposal Functions of the EDS 3000 Maintenance and servicing Assembly 9.1 General installation notes 9.2 Additional installation instructions Operating elements of the EDS 3000 Operation modes 11.1 SIO mode 11.2 SDCI-Mode Parameterisation 12.1 General 12.2 Parameterisation in SDCI mode 12.3 Parameterisation in SIO Mode...
  • Page 37 22.2 EDS 3000 with thin-film strain gauge; relative pressure 22.3 Relevant data for IO-Link Model Code 23.1 EDS 3000 with ceramic sensor cell; absolute and relative pressure up to 16 bar (500 psi) 23.2 EDS 3000 with thin-film strain gauge; relative pressure Device dimensions Zubehör...
  • Page 38 EDS 3000 IO-Link Preface The instructions provide you, as user of our product, with key information on the operation and maintenance of the equipment. It will acquaint you with the product and assist you in obtaining maximum benefit in the applications for which it is designed.
  • Page 39: Safety Information

    EDS 3000 IO-Link Safety Information Before commissioning, check the device and all accessories supplied. Before commissioning, please read the operating instructions. Ensure that the instrument is suitable for your application. If the instrument is not handled correctly, or if the operating instructions and specifications are not adhered to, damage to property and/or personal injury can result.
  • Page 40: Intended Use / Foreseeable Misuse

    EDS 3000 IO-Link The symbol indicates important information or features and application suggestions for the product used. The symbol means that appropriate ESD-protective measures must be considered according to DIN EN 100 015-1. (Cause of a potential equalisation between body and device-mass as well as the housing-mass about a high-impedance resistance (approx.
  • Page 41: Organisational Measures

    Transportation, Packaging, Storage 5.1 Transport The EDS 3000 sensor is supplied in a rugged cardboard box. When receiving and unpacking, make sure the item has been delivered in full and look out for any possible transport damage. If present, immediately show it to the shipper.
  • Page 42: Functions Of The Eds 3000

    When installing using a Minimess hose, the housing must be earthed separately (e.g. with a screened cable). Caution! Installation of the EDS 3000 must be carried out using a spanner (AF 27) suiting the hexagonal nut of the pressure port. CAUTION !
  • Page 43: Additional Installation Instructions

    When connecting the Class B Ports, 3 core leads with PIN 1, 3 and 4 may be used only. Configuring pin 2 as an additional analogue output, this may no more be connected with the master under any circumstances. Operating elements of the EDS 3000 Display of Pressure unit 4-digit...
  • Page 44: Operation Modes

    4 to the connected IO-Link master. The EDS 3000 provides a process data width of 2 bytes. 14 bits are used for the actual measured value ("PDV" = "Process data value"). The number of decimal places used is based on the measuring range and can be taken from the device description file (IODD).
  • Page 45: Parameterisation

    The Zip file has an additional PDF file with an IODD description. 12.3 Parameterisation in SIO Mode If IO-Link is not used, the EDS 3000 IO-Link functions as a pressure switch with two switching outputs or with 1 switching output and 1 analogue output.
  • Page 46: Parameterisation With Zbe P1-000

    EDS 3000 IO-Link 12.5 Parameterisation with ZBE P1-000 (Connection via standard cable) Q2 / QA ZBE P1 Device Q1 / C Reading the digital display Representation ASCII Designation 7-segment representation display SP 1 Switch point, output 1 RP 1 Switch-back point, output 1...
  • Page 47 EDS 3000 IO-Link Representation ASCII Designation 7-segment representation display UN , Unit conversion Unit in bar Unit in MPa PS , Unit in psi Max. value Error indication D ,S Display Reset RS.XL Reset max value rS.HL Programming disable Keys locked...
  • Page 48: Output Signals

    EDS 3000 IO-Link Output Signals 14.1 Switching outputs The ENS 3000 IO-Link has 2 switching outputs whose switching behaviour (window mode or two-point mode) is parameterisable. Note: If the sensor is operated at the Class-B port of an IO-Link master, pin 2 of the...
  • Page 49: Window Mode - Window Function Setting (Fno / Fnc)

    EDS 3000 IO-Link Note: It is only possible to set the switch point (SP) if it is higher than the respective switch-back point (RP). 14.1.2 Window mode - Window function setting (Fno / Fnc) The window function enables a range to be monitored. An upper and a lower switch point which defines the range can be assigned to each switching output.
  • Page 50: Setting Ranges For The Switching Outputs

    EDS 3000 IO-Link 14.2 Setting ranges for the switching outputs Measurement Lower limit of Upper limit of Minimum Increment* range RP / FL SP / FH difference betw. RP and SP or FL and FH in bar in bar in bar in bar - 1 ..
  • Page 51: Basic Settings

    EDS 3000 IO-Link Basic Settings The EDS 3000 can be adapted to suit the particular application as required by changing multiple settings. These settings are combined in a menu. 15.1 Main menu The range is not displayed if "i" or "u"...
  • Page 52: Add-On Functions

    EDS 3000 IO-Link 15.2 Add-on functions The range is not displayed if "i" or "u" is pre-set under "ou2" in the "extended functions". Status: 2022-07-14 HYDAC ELECTRONIC GMBH Part no.: 669897...
  • Page 53: Changing The Basic Settings

    EDS 3000 IO-Link Changing the Basic Settings Note If no key has been pressed for approx. 60 seconds, the menu closes automatically, and any changes that may have been made will not be saved. Resetting the peak value The pressure peak value can be reset.
  • Page 54: Program Enable

    EDS 3000 IO-Link Program enable 18.1 General The instrument has a program enable which must be set to change the settings. The program enable can be set or cancelled during operation. It provides protection against unintentional alterations of settings. 18.2 Changing the Programming Enable ...
  • Page 55: Error Messages

    EDS 3000 IO-Link Error Messages If an error is detected, a corresponding error message appears which must be acknowledged by pressing any key. Possible error messages are as follows: E.10 A data error has been detected in the saved settings. Possible causes are strong electromagnetic interference or a defective component.
  • Page 56: Pin Connection

    EDS 3000 IO-Link PIN connection M12x1, 4 pole Q1/C Q2/QA Signal Designation Q2/QA Switching output (SP2) / analogue output Q1/C Switching output (SP1) / IO-Link Communication Status: 2022-07-14 HYDAC ELECTRONIC GMBH Part no.: 669897...
  • Page 57: Technical Data

    EDS 3000 IO-Link Technical Data 22.1 EDS 3000 with ceramic sensor cell; absolute and relative pressure up to 16 bar (500 psi) Input data Ceramic sensor at absolute pressure Measuring ranges Overload pressure Burst pressure Ceramic sensor at relative pressure -1..1...
  • Page 58 EDS 3000 IO-Link Environmental Conditions Compensated temperature range -10 .. +70 °C [-14 .. +158º F] Operating temperature range -25 .. +80 °C [-13 .. +176º F] (-25 .. +60 °C acc. to UL spec.) Storage temperature range -40 .. +80 °C [-40 .. +176º F] Fluid temperature range -25 ..
  • Page 59 EDS 3000 IO-Link 22.2 EDS 3000 with thin-film strain gauge; relative pressure Input data Measuring ranges -1 .. 1 1000 Overload pressure 1000 1200 100 100 100 100 125 1250 2000 2000 3000 Burst pressure bar Measuring ranges 1000 3000...
  • Page 60 EDS 3000 IO-Link Other data Supply voltage 9 .. 35 V DC without analogue output 18 .. 35 V DC with analogue output when applied acc. to UL specifications - limited energy - acc. to 9.3 UL 61010; Class 2;...
  • Page 61: Eds 3000 With Ceramic Sensor Cell; Absolute And Relative Pressure Up To 16 Bar

    EDS 3000 IO-Link Model Code 23.1 EDS 3000 with ceramic sensor cell; absolute and relative pressure up to 16 bar (500 psi) NOTE The EDS 33XX sensor series have been replaced by the EDS 34XX series with the corresponding pressure range. Repeat orders are therefore no more possible for EDS 33X6 sensors.
  • Page 62: Eds 3000 With Thin-Film Strain Gauge; Relative Pressure

    EDS 3000 IO-Link 23.2 EDS 3000 with thin-film strain gauge; relative pressure EDS 3 4 X 6 - F31 - XXXX - XXX Version (technology) = Thin film DMS relative Mechanical connection = G1/2 B DIN EN 837 (only in conjunction with pressure range in bar)
  • Page 63: Device Dimensions

    EDS 3000 IO-Link Device dimensions Display adjustable 270° Housing adjustable 340° 6hex-SW27 Elastomer profile seal ring Diameter connector M12x1 4 pole 6hex-SW27 Status: 2022-07-14 HYDAC ELECTRONIC GMBH Part no.: 669897...
  • Page 64: Zubehör

    EDS 3000 IO-Link Zubehör 25.1 Electrical connection ZBE 06 (4 pole) Mating connector M12x1, right angle Cable diameter: 3.3 .. 6.6 mm (0.13 .. 0.26 inch) Part No.: 6006788 ZBE 06-02 (4 pole) Mating connector M12x1, right- angle with 2 m (78.7 inch) cable, Part No.: 6006790...
  • Page 65 EDS 3000 IO-Link ZBM 3100 Clamp for wall-mounting,weld-type fitting (Material of welding bridge: QSTE340TM, zinc coating EN 12329 FE/ZN8/B; Material of lower section: TPE Santoprene 10187; Material of top section: Steel strip DIN 95381-1.4571) Part no.: 3184632 ZBM 3200 Splash guard (Material: Elastollan S60 A15 SPF 000) Part no.: 3201919...
  • Page 66: List Of Abbreviations

    EDS 3000 IO-Link List of abbreviations Value window upper value Value window lower value Window function, N/C Window function, N/O Full Scale IODD IO Device Description ISDU Indexed Service Data Unit Output function Switch-back point SDCI Single-drop digital communication interface...
  • Page 67: Contact

    EDS 3000 IO-Link Contact HYDAC ELECTRONIC GMBH Hauptstrasse 27 D-66128 Saarbruecken Germany Web: www.hydac.com Email: electronic@hydac.com Phone: +49 (0)6897 509-01 Fax.: +49 (0)6897 509-1726 HYDAC Service For enquiries about repairs or alterations, please contact HYDAC Service. HYDAC SYSTEMS & SERVICES GMBH...
  • Page 68: Anhang / Annex: Iodd Einstellparameter / Iodd Setting Parameters

    EDS 3000 IO-Link Anhang / Annex: IODD Einstellparameter / IODD Setting Parameters Die Einstellparameter des EDS 3000 fin- The setting parameters of the EDS 3000 can den Sie auf den nachfolgenden Seiten. be found on the following pages. Die komplette IODD steht zum Download...
  • Page 69 EDS 3000 IO-Link Standard Variable "Device Access Locks" index=12 id=V_DeviceAccessLocks data type: 16-bit Record (subindex access not supported) access rights: rw subindex bit offset data type name description Parameter (write) Boolean Access Lock Datenhaltung (Subindex 2) ist aus Kompatibilitätsgründen vorhanden und sollte immer auf...
  • Page 70 EDS 3000 IO-Link Variable "BDC2 Thresholds" index=62 id=V_Bdc2Thresholds data type: 32-bit Record (subindex access not supported) access rights: rw modifies other variables excluded from data storage allowed default subindex data type mod. other var. name description offset values value Lower limit of...
  • Page 71 EDS 3000 IO-Link allowed default subindex data type mod. other var. name description offset values value 0 = Normally 8-bit Open, 1 = V_Bdc1Behavior Direction UInteger Normally Closed 2 = Window, 8-bit 3 = Two- V_Bdc1Behavior Mode UInteger Point 16-bit Integer 25..2475...
  • Page 72 EDS 3000 IO-Link Variable "SP States" index=72 id=V_SpStates data type: 8-bit Record (subindex access not supported) access rights: ro dynamic subindex bit offset data type default value name description Primary Value Boolean false Primary Value Boolean false Octet 0 bit offset...
  • Page 73 EDS 3000 IO-Link Variable "Primary Value Display Unit" index=76 id=V_PrimaryValueDspUnit data type: 8-bit UInteger allowed values: 0 = bar, 1 = psi, 2 = MPa default value: 0 access rights: rw octet bit offset 7 - 0 element bit 7 - 0 Variable "Primary Value Range"...
  • Page 74 EDS 3000 IO-Link Variable "Primary Maximum Value" index=92 id=V_PrimaryMaxValue data type: 24-bit Record (subindex access not supported) access rights: ro dynamic allowed default mod. subindex data type name description offset values value other var. 16-bit Integer Process Value Boolean false...
  • Page 75 EDS 3000 IO-Link ErrorTypes Additional Code Name Description code Device application error - Service has been refused by the device application and no 128 (0x80) 0 (0x00) no details detailed information of the incident is available 128 (0x80) 17 (0x11)
  • Page 76 EDS 3000 IO-Link Events Code Type Name Description 36002 (0x8ca2) Error User setup error User setup is corrupt, device is running with factory settings Primary value signal 36016 (0x8cb0) Error Primary value update failed, device output is temporarily disabled error...