Technical Manual
Room Temperature Controller

4.4.4 Lock objects

The following settings are available:
Figure 13: Settings – Lock objects
The following chart shows the dynamic range for this parameter:
ETS-text
Heating disable object
Cooling disable object
Table 25: Settings – Lock objects
By activating the lock objects, the user has one or two lock objects available for locking the control
value, depending on the setting of the controller type. These lock objects serve to prevent the
actuators (heating device or cooling device) from starting up undesirably. For example, if the heating
is not to start in certain situations, e.g. when the window is open, the lock object can be used to lock
the control value. Another application of the lock object is, for example, manual locking, e.g. via a
push-button, in the event of a cleaning process. The lock object locks the control value as soon as a
"1" is sent to the associated 1-bit communication object.
The following communication objects are available for this:
Number Name
14
Heating disable object
15
Cooling disable object
Table 26: Communication objects – Lock objects
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 • Germany
23
Phone: +49-2263-880 • knx@mdt.de • www.mdt.de
[SCN-RT1xPx.01]
Dynamic range
[default value]
▪ inactive
▪ active
▪ inactive
▪ active
Length
1 Bit
1 Bit
Comment
Activates the lock object for the
heating process.
Activates the lock object for the
cooling process.
Usage
Locks the control value heating
Locks the control value cooling