Technical Manual
Room Temperature Controller
4.2 Temperature measurement
The following settings are available at the ETS-Software:
Figure 6: Settings – Temperature measurement
The following table shows the available settings:
ETS-text
Send actual value after
change of
Send actual temperature
cyclically
Send min/max value
Internal sensor correction
value (value*0,1K)
Internal/external sensor
Table 3: Settings – Temperature measurement
Send actual value after change of
This function sets when the current temperature value shall be sent. By choosing the setting
"disable", no value will be sent at all.
Send actual temperature cyclically
You can activate this function by choosing a time. Now, the room temperature controller sends the
current temperature periodically after the adjusted time. This function is independent from the
function "Send actual value after change of". So the temperature controller will send its current
value also if there is no change of it.
Internal sensor correction value (value*0,1K)
You can correct the measured temperature value by this setting. By choosing a negative value for this
parameter, the measured value will be lowered and by choosing a positive value, the measured value
will be lifted. The value is multiplied by 0,1K, so the current value can be lowered or lifted up to 5K.
This setting is useful, when the sensor was built at an unfavourable location, e.g. becoming draft or
next to a window. When this function is activated, the temperature controller will also send the
corrected values.
All sensors are matched in-plant to 0,1K.
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 • Germany
10
Phone: +49-2263-880 • knx@mdt.de • www.mdt.de
[SCN-RT1xPx.01]
Dynamic range
[default value]
Disable, 0,1K – 2,0K
Disable, 1 min – 60 min
▪ Disable
▪ Send enable
-50 ... 50
[0]
▪ 100% intern
▪ 90% intern/ 10% extern
▪ 80 % intern/ 20% extern
▪ ...
▪ 100% extern
Comment
Sending condition for the actual
temperature value.
Activation of the cyclic sending of
the temperature value.
Activation of the sending of
min/max values.
Correction of the internal sensor.
Adjustment of the balance
between internal and external
sensor.