Technical Manual
Room Temperature Controller

4.5.2 PI control continuous

The following picture shows the available settings (here for controller type "Heating"):
Figure 21: Settings – PI control continuous
The table shows the available settings:
ETS-text
Direction of controller
Max value of control
value
Heating system
Cooling system
Proportional range (K)
Reset time (min)
Send control value
cyclic
Use additional level
Table 34: Settings – PI control continuous
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 • Germany
29
Phone: +49-2263-880 • knx@mdt.de • www.mdt.de
[SCN-RT1xPx.01]
Dynamic range
[default value]
▪ normal
▪ inverted
100%; 90%; 80%; 75%; 70%; 60%; 50%;
40%; 30%; 25%; 20%; 10%; 0%
▪ Warm water heating
(4K/120min)
▪ Underfloor heating (4K/150min)
▪ Split Unit (4K/60min)
▪ Adjustment via control parameter
▪ Split Unit (4K/60min)
▪ Cooling ceiling (4K/150min)
▪ Adjustment via control parameter
1 K – 8 K
[ 2K]
15 min – 210 min
[150 min]
Disable, 1 min – 60 min
▪ No
▪ Yes
Comment
Defines the controlling behavior
with rising temperature
4.5.5 Direction of
controller.
Indicates the output power of the
manipulated variable in
maximum operation.
Setting of the used heating
system.
Individual configuration available
via "Adjustment via control
parameter"
Setting of the used cooling
system.
Individual configuration available
via "Adjustment via control
parameter"
With selection "Adjustment via
control parameters". Free setting
of the proportional range.
With selection "Adjustment via
control parameters". Free setting
of the reset time.
Activation of whether the control
value is to be sent cyclically.
Activation of an additional
control level possible.
Only available in "Heating"
mode