Figure 3-5 Expansion bolt composition
(1) M12 bolt
Knock the expansion bolt into the hole until the expansion sleeve completely fits into the hole.
The expansion sleeve must be completely buried under the ground to facilitate subsequent
installation.
Figure 3-6 Installing an expansion bolt (unit: mm)
1.
2.
3.
4.
Step 3 Use a pallet truck to move the cabinet to the installation position.
Issue 01 (2020-03-06)
(2) Spring washer
Drill holes in the ground by using a hammer drill. The hole depth is 52 mm to 60 mm.
Partially tighten the expansion bolt and vertically insert it into the hole. Knock the
expansion bolt using a rubber mallet until the expansion sleeve is fully inserted into the
hole.
Partially tighten the expansion bolt.
Remove the bolt, spring washer, and flat washer.
Copyright © Huawei Technologies Co., Ltd.
(3) Flat washer
(4) Expansion sleeve