(13) RS485 port
(17) Battery temperature
sensor port

2.3.5.2 ECM

Appearance
The control module consists of two energy control modules (ECMs) in active/standby mode.
Figure 2-13 ECM
Table 2-4 Ports on the ECM
Silk Screen
PARALLEL
BSC
Table 2-5 Indicator description
Indicator
NORMAL
Issue 01 (2020-03-06)
Ports are protected by a security mechanism.
Description
The PARALLEL port transmits parallel signals between racks.
The BSC port is used in a dual-bus system to synchronize output
frequencies and phases between UPS systems, ensuring that two buses
can switch with each other.
BSC cables are hot-swappable.
For a single UPS, the parallel cable is not needed.
Color
Green
Copyright © Huawei Technologies Co., Ltd.
(14) Fast Ethernet (FE)
port
(18) Optional card
subrack cover
Status
Description
Steady on
This ECM is the active ECM.
Blinking at
This ECM is the standby ECM and it is ready.
0.5 Hz
(15) COM2
(16) COM1 port
port