UPS5000-S-300 kVA User Manual
(3P3W, 200 V)
Alarm ID
Alarm Name
(Alarm
ID-Cause
ID)
0359
No power supplied
0332
Output disabled
0337
PDC bypass input
breaker open
0338
PDC output breaker
open
0341
PDC Maint. breaker
closed
0342
Mains input breaker
open
0343
BPM input breaker
open
0340
Maint. breaker
closed
0335
Generator
connected
0594-1
Insufficient
redundant racks
0095-1
Insuffi. redundancy
Issue 01 (2020-03-06)
Severity
Cause
Warning
No power is
supplied.
Minor
The output is
disabled.
Critical
The bypass input
circuit breaker on
the PDC is OFF.
Critical
The output circuit
breaker on the PDC
is OFF.
Minor
The maintenance
circuit breaker on
the PDC is ON.
Critical
The mains input
circuit breaker is
OFF.
Critical
The bypass input
circuit breaker is
OFF.
Minor
The maintenance
circuit breaker is
ON.
Warning
The generator is
connected.
Minor
The load is
excessive.
The configured
number of
redundant racks
is incorrect.
Minor
The load is
excessive.
The configured
number of
redundant
Copyright © Huawei Technologies Co., Ltd.
A Alarm List
Solution
other alarms.
The running status is displayed.
See details about how to handle
other alarms.
The running status is displayed.
See details about how to handle
other alarms.
The running status is displayed.
No further measures are required.
1. Check that all UPS output
circuit breakers are ON.
2. On the LCD, check that PDC
output breaker open alarm
has disappeared. If the alarm
persists, tap the Clear Fault
button to clear the alarm.
The running status is displayed.
No further measures are required.
The running status is displayed.
No further measures are required.
The running status is displayed.
No further measures are required.
The running status is displayed.
No further measures are required.
The running status is displayed.
No further measures are required.
1. Reduce the load.
2. Decrease the configured
number of redundant racks.
1. Reduce the load.
2. Decrease the configured
number of redundant modules.
160