Dépannage
LE COMPRESSEUR S'AR-
LA TEMPÉRATURE DE L'EAU
RÊTE EN RAISON DE L'IN-
EN SORTIE EST SUPÉRIEURE À
TERVENTION DU PRESSOSTAT
LA VALEUR PROGRAMMÉE
HAUTE PRESSION
NON
DÉBIT D'EAU EXCESSIF,
CHARGE THERMIQUE
ÉLEVÉE
OUI
DIMINUER LE
DÉBIT DU
FLUIDE À
REFROIDIR
TEMPÉRATURE
AMBIANTE
ÉLEVÉE
OUI
RAMENER LA
TEMPÉRATURE
AMBIANTE SOUS
LA VALEUR
LIMITE DÉCLARÉE
Hyperchiller 076-116
PANNE
LE COMPRESSEUR S'ARRÊTE EN
RAISON DE L'INTERVENTION DU
PRESSOSTAT PRESSION BASSE
NON
PRESSOSTAT
FILTRE RÉFRIGÉ-
CASSÉ OU
RANT COLMATÉ
DÉRÉGLÉ
OUI
OUI
REMPLACER LE
PRESSOSTAT
NON
NON
AILETTES DU
CONDENSATEUR
SALES
OUI
OUI
NETTOYER LES
AILETTES DU
CONDENSATEUR
REMÈDE
CAUSE
NON
NON
NON
DÉBIT D'EAU
INSUFFISANT
OUI
AUMENTARE LA
REMPLACER
PORTATA DEL FLUI-
DO DA RAFFRED-
LE FILTRE
DARE
NON
VENTILATEUR
SURFACE DU
TOURNANT EN
CONDENSEUR
SENS INVERSE
BOUCHÉE
OUI
LIBÉRER LA
INVERSER
SURFACE
LES PHASES
FRONTALE DU
CONDENSATEUR
ASPIRATION
COMPRESSEUR,
LIGNE LIQUIDE
GIVRÉES
BULBE
VANNE
THERMOSTA-
THERMOSTATIQUE
TIQUE DÉCHARGÉ
DÉRÉGLÉE
OUI
OUI
NON
RÉGLER DE
REMPLACER
NOUVEAU LA
LA VANNE
VANNE
NON
FUITES DANS LE CIRCUIT,
INSTALLATION DÉCHARGÉE
OUI
CONTRÔLER LA
PRÉSENCE DE
FUITES, LES ÉLIMINER,
CHARGER LE
CIRCUIT
10/10
LE COMPRESSEUR FONC-
TIONNE
LONGUEMENT
ET BRUYAMMENT
COMPOSANTS DE
COMPRESSEUR
ENDOMMAGÉS
OUI
NON
RÉPARER OU
REMPLACER LE
COMPRESSEUR
FILTRE
RÉFRIGÉRANT
COLMATÉ
OUI
REMPLACER
LE FILTRE