Parker Hyperchill ICE076 User Manual page 20

Pco5 (50hz)
Hide thumbs Also See for Hyperchill ICE076:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 13
English
5
Option
5.1 Precision Control
(Control pCOS)
5.1.1 Direct parameter (DIRECT)
PARAMETER
CODE
Temperature control set point
SEt
Temperature control differential
dIF
5.2 Low ambient temperature (-10C°)
(Control pCOS)
5.2.1 Direct parameter (DIRECT)
PARAMETER
CODE
Temperature control set point
SEt
Temperature control differential
dIF
Set fan pressure switch
P1: OFF 14 °C ; ON 18 °C
P2: OFF 15 °C ; ON 19 °C
P3: OFF 16 °C ; ON 20 °C
5.3 Precision Control + Low ambient temperature
(-10C°)
(Control pCOM)
5.3.1 Direct parameter (DIRECT)
PARAMETER
CODE
Temperature control set point
SEt
Temperature control differential
dIF
5.3.2 Fan set, factory parameter (FACTORY)
PARAMETER
CODE
Set I° fan step
SEF1
Set 2° fan step
SEF2
Set 3° fan step
SEF3
Differential
dIF
P1 : OFF 15 bar - ON 19bar
P2 :
OFF 16 bar - ON 20bar
P3 :
OFF 17 bar - ON 21 bar
Hyperchiller 076-116
5.4 Low ambient temperature L2 (-20/30 C°)
(Control pCOM)
5.4.1 Direct parameter (DIRECT)
PARAMETER
Temperature control set point
TYPE DEFAULT
Temperature control differential
D
20.0
Fan Set control:
D
1.0
Pressure 14bar - Fan operation 0%
Pressure 20bar - Fan operation 100%
5.4.2 b5 probe parameters, service parameter (USER)
Ambient temperature probe
PARAMETER
TYPE DEFAULT
High temperature alarm
D
7.0
Low temperature alarm -20
D
4.0
Low temperature alarm -30
Sensor calibration
TYPE DEFAULT
D
20.0
D
1.0
TYPE DEFAULT
F
19.0
F
20.0
F
21.0
F
3.0
CODE
TYPE DEFAULT
SEt
D
7.0
dIF
D
4.0
CODE
TYPE
DEFAULT
HA5
U
60.0
-20.0
LA5
U
-30.0
CA5
U
0.0
8/10

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hyperchill ice090Hyperchill ice116Ice090c4003501p30ff000000Ice076a4003500000ff000000Ice076a4003501p30ff000000Ice076a4003501p30ff000lw0 ... Show all

Table of Contents