Change The Type Of Trigger - Omron V430-F Series User Manual For Communication Settings

Autofocus multicode reader
Hide thumbs Also See for V430-F Series:
Table of Contents

Advertisement

2 Controlling Operation and Data Output with Parallel
2-1-4

Change the Type of Trigger

It is possible to change the Input method for the trigger used by the code reader to execute Image
capture.
• WebLink - Setup - Gear Icon - Advanced Settings - Read Cycle - Trigger
Setting Item
Mode
External Trigger Sig-
nal Filter (Rising
Edge)
External Trigger Sig-
nal Filter (Falling
Edge)
External Trigger
State
2 - 6
Setting Value
Continuous Read
With no Parallel TRIG signal used, the code reader executes
Continuous Read.
The data is continually output as each code is read.
Continuous Read 1
With no Parallel TRIG signal used, the code reader executes
Output
Continuous Read.
If the data of a read code is the same as the previously read
code, it is not output.
External Level
While TRIG signal is ON, Read is executed.
When TRIG signal turns OFF, Read ends.
External Edge
While TRIG signal is ON, Read is executed.
On Good Read or when End of Read Cycle condition is met,
Read ends.
Serial Data
Read is executed when you send the serial command "<>" (de-
fault value) to the code reader
On Good Read or when End of Read Cycle condition is met,
Read ends.
Serial Data and
Read is executed when TRIG signal turns ON or when you send
Edge
the serial command "<>" (default value) to the code reader
On Good Read or when End of Read Cycle condition is met,
Read ends.
Continuous Read
With no Parallel TRIG signal used, the code reader executes
Auto
Continuous Read.
Exposure time and Gain is automatically adjusted for every Read
performed.
0 to 2097120 μs
When the TRIG signal is ON for more than a set time, the trigger
is input as ON.
If it is ON for less than the set time, it is not regarded as ON, so
no trigger is input.
0 to 2097120 μs
When the TRIG signal is OFF for more than a set time, the trigger
is input as OFF.
If it is OFF for less than the set time, it is not regarded as OFF, so
no trigger is input.
Active Open
When the TRIG signal turns from OFF → ON, it is recognized as
the rising edge of the Trigger.
When the TRIG signal turns from ON → OFF, it is recognized as
the falling edge of the Trigger.
Active Closed
When the TRIG signal turns from ON → OFF, it is recognized as
the rising edge of the Trigger.
When the TRIG signal turns from OFF → ON, it is recognized as
the falling edge of the Trigger.
V430-F Series Autofocus Multicode Reader User Manual for Communication Settings