BACnet Server – Modbus Client
5.2.2 Analog Input Object Type
Property Identifier
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Status_Flags
Event_State
Reliability
Out_Of_Service
Units
COV_Increment
Time_Delay
Notification_Class
High_Limit
Low_Limit
Deadband
Limit_Enable
Event_Enable
Acked_Transitions
Notify_Type
Event_Time_Stamps
Event_Detection_Enable
Property_List
1
Only available when specific object has a Notification Class configured
2
Only available in some models after activations on the configuration tool, review the specific model manual for
details.
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
Property Datatype
BACnetObjectIdentifier
CharacterString
BACnetObjectType
REAL
CharacterString
BACnetStatusFlags
BACnetEventState
BACnetReliability
BOOLEAN
BACnetEngineeringUnits
REAL
Unsigned
Unsigned
REAL
REAL
REAL
BACnetLimitEnable
BACnetEventTransitionBit
s
BACnetEventTransitionBit
s
BACnetNotifyType
BACnetArray[N] of
BACnetTimeStamp
BOOLEAN
BACnetARRAY[N] of
BACnetPropertyIdentifier
Value
(Analog Input, 0)
Configurable through Config Tool
ANALOG_INPUT (0)
x
Configurable through Config Tool
{FALSE, FALSE/TRUE, FALSE, FALSE}
STATE_NORMAL (0)
NO_FAULT_DETECTED (0),
UNRELIABLE_OTHER (7)
FALSE
Configurable through Config Tool
0
-
-
-
-
-
-
{TRUE, TRUE, TRUE}
-
-
-
-
-
User Manual r1.10 eng
ASHRAE IBOX
R
R
R
R
R
R
R
R
2
O
R
R
R
R
R
O
R
R
R
R
R
O
W
1
O
R
1
O
R
1
O
R
1
O
R
1
O
R
1
O
R
1
O
R
1
O
R
1
O
R
1
O
R
O
R
R
R