Auxiliary switch ("b" contact)
Auxiliary switch ("a" contact)
UVT controller voltage application
For 100-120 V AC
For 200-240 V AC
For 380-460 V AC
DC ratings
Apply voltage
IN2
IN1
External unit
Apply voltage
OUT4
OUT3
D2
D1
D2
D1
Control circuit terminal block
Applicable crimp terminal
Applicable crimp-type terminals
for M3.5 screws with an outer
diameter of 7.2 mm or less.
A
A
(Wire size 1.25 mm
2
to 2.0 mm
A = 7.2 mm or less
43
33
23
13
341
44
34
24
14
344 342 334 332 324 322 314 312
For the drawout type, the cables should have the length which allow the control circuit terminal
˜
block to be moved to the left or right by 5mm.
When a coil load is connected in the same control circuit as the ETR, surge absorbers are required
˜
to absorb the surge voltage.
OCR alarm (AL)
˜
The contact output of the OCR alarm (Standard type AL) is the one-pulse output and the output
time is 30~50ms.
For this reason, this output needs self-holding circuit.
˜ For Power supply type P3 and P4, the high sensitive relay used in contact output may cause the
chattering noise (wrong output of 1ms level) during ON and OFF operation, depending on the
Panel placing condition. When it is used in the quick responsive sequence, the lter circuit of a
few milli-second (ms) should be provided or the double reading sampling should be implemented.
Closing coil (CC)
˜
As CC is one-pulse driven, it is not necessary to insert AXb for burning prevention purposes.
Inserting AXb will cause anti-pumping function to be ineffective.
Under voltage trip device (UVT)
˜
Use the switch that can open and close 150V DC, 0.5A for remote trip.
Remote trip terminal has short bar at shipment, so remove it before using this function.
Disconnect the voltage input wires during dielectric testing of main circuit.
˜ Since some terminals are polarized, the wiring should be done correctly as the polarity shown in the
wiring diagram when the control voltage is DC. Auxiliary switch (AX) Standard type has no polarity.
˜ Alarm reset (Terminal: RS1 and RS2 ) is available only for Power supply type P3, P4 and P5.
For Power supply type P1 and P2, it can not be reset from the Control circuit terminal block ( RS1 and RS2 ).
Alarm contacts (Terminal :
˜
.
P5
˜ FG (Terminal: P4 ) is the protective earth for power supply (Terminal: P1 , P2 ).
It is recommended to use this terminal to reduce surge (M8 screw required).
2
)
Shorting b-contact (SBC)
˜
SBC can be provided for all AX b contacts. At the time of shipment from factory, SBC is already
connected to control circuit terminal block. Only one more crimp terminal can be added on
contact, overlapping with SBC's contact on Terminal: 11 ~ 51 .
331
321
311
Cell switch
~
) are available only for power supply type
513
574
Cell switch
,
and
P3
P4
E-33