Characteristics Setting For The Wf Type - Mitsubishi Electric AE-SW Series Instruction Manual

Hide thumbs Also See for AE-SW Series:
Table of Contents

Advertisement

Characteristics setting for the WF type

12
G
7
4
8
5
9
6
10
2
1
11
3
13
16
15
14
Trip indicator LED
Pre-alarm LED
Temperature alarm LED
Load current LED
RUN LED
ERR. LED
Current setting dial
LTD time setting dial
LTD curve setting dial
STD pick-up setting dial
STD time setting dial
INST/MCR pick-up current setting dial
Optional setting module
Pre-alarm current setting dial
RESET button (TEST L/S LOCK button)
TEST terminal
Note)
The figure shows WF1 type with G1 module, Display (DP1) and MCR switch.
G1, DP1 and MCR are optional equipments.
Table 26
No.
Setting item
Symbol
Current setting
Ir
LTD time
T
L
a
LTD curve setting
STD pick-up
Isd
current
STD time
Tsd
INST/MCR
Ii
pick-up current
Pre-alarm current
Ip
Pre-alarm time
Tp
Remark (1) The table and the figure include both optional display and MCR.
Remark (2) For WF relay, when Pre-alarm current Ip is set at "OVER", the Ip value is "Ir x 1.15".
Relation of setting dial
In (CT rating)
Ir
Ig (P.28)
Isd
Ii
E-26
The selectable
characteristics are the
following five curves.
(I
4
-1)t = const.
(I
3
-1)t = const.
(I
2
-1)t = const.
(I -1)t = const.
( I
0.02
-1)t = const.
I (current)
LTD characteristics curves
LTD curve can be selected
by the LTD curve setting dial.
Characteristic setting range
0.5 ~ 1.0 (0.05step) x In (CT rating)
LTD pick-up current : 1.15 x Ir
1–2–3–4–5–6–8–10–12–15–18s
0.02–1–2–3–4
1.5–2–2.5–3–4–5–6–7–8–9–10 x Ir
0.5–0.4–0.3–0.2–0.1–0.06–0.06–0.1–0.2–0.3–0.4–0.5s
(I
t ON)
2
AE630-SW~AE1600-SW
16-12-10-8-6-4-2-2-4-6-8-10-12-16
AE2000-SW~AE3200-SW
AE4000-SW
AE2000-SWA, AE4000-SWA
AE5000-SW
AE6300-SW
Ir x 0.68 ~ 1.0 (0.04step) –OVER
1/2 T
at Ir x 4 (after 1/2 T
L
Ip
Ip2 (P.29)
Load current LED (60, 80, 100%, OVER)
[LTD curve setting "a=2"]
a=2
10000
5000
4000
Pre-alarm current : Ip
3000
Ir x 0.68~1.0(0.04step)-OVER 5%
2000
Current setting : Ir
0.5~1.0(0.05step) x In(CT rating)
1.10 x Ir ... Non pick-up
LTD pick-up
1.20 x Ir ... Pick-up
1000
500
400
300
200
100
LTD operating time t
Note1
LTD
a
(4/1.1155)
-1
60
t
=
x T
LTD
L
a
50
(I/1.1155Ir)
-1
Accuracy :
40
a = 2
30%(1.5Ir load current<4Ir)
I = load current (A)
30
20%(4Ir load current)
Ir= 0.5~1.0 x In (A)
T
= 1~18 (s)
L
20
PAL operating time t
Note2
PAL
a
(4Ir/0.97lp)
-1
t
=
x T
PAL
L
a
10
(I/0.97lp)
-1
Accuracy :
a = 2
30%(1.5Ir load current<4Ir)
I = load current (A)
20%(4Ir load current)
Ip= 0.68~1.15 x Ir (A)
5
T
= 1~18 (s)
L
4
3
2
1
STD time : Tsd
0.06-0.1-0.2-0.3-0.4-0.5(s) 20%
.5
.4
.3
STD pick-up current : Isd
Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 15%
.2
.1
.05
.04
Note1 : LTD operating time is 0.8s(FLAT)when the operating
.03
time becomes 0.8s or less.
Note2 : PAL operating time is 0.5s(FLAT) when the operating
.02
time becomes 0.5s or less.
Note3 : When Tsd ="0.06" setting,operating time is 0.04~0.08s.
I
2
t is selectable ON or OFF.
.01
1
2
5
10
20
at Ir x 4
(I
t OFF)
2
at Isd x 1.5
x Ir
(INST)
(MCR)
12-10-8-6-4-2-2-4-6-8-10-12
x Ir
(INST)
(MCR)
10-8-6-4-2-2-4-6-8-10
x Ir
(INST)
(MCR)
, PAL contact output turns on.)
L
Pre-alarm time : Tp
T
/2 20%
L
LTD time : T
L
1-2-3-4-5-6-8-10-12-15-18(s) 20%
Note3
(at Isd x 1.5)
I
2
t ON
(ramp)
I
2
t OFF
INST/MCR pick-up current : Ii
Max. breaking time
Ir x 2-4-6-8-10-12-16 15% : WF1
(In case of AE4000-SW~
Ir x 2-4-6-8-10-12
15% : WF2
6300-SW, it is 0.05s)
Ir x 2-4-6-8-10
15% : WF3
50
100
150
500
1000
2000
125
200
1600
Current (%)
Accuracy
1.10 x Ir ... Non Pick-up
1.20 x Ir ... Pick-up
±30% (1.5Ir≦load current<4Ir)
±20% (4Ir≦load current)
±15%
±20%
It operates in the range
between 0.04 and 0.08
when the time set at 0.06s.
WF1
±15%
WF2
WF3
±5%
±30% (1.5Ir≦load current<4Ir)
±20% (4Ir≦load current)
(at Ir x 4)
(at Ir x 4)
With MCR
5000
10000
Factory default
value
1.0
18
2
10
0.5 (I
2
t ON)
WF1 ... 16 (INST)
WF2 ... 12 (INST)
WF3 ... 10 (INST)
OVER