Wiring Diagram - Mitsubishi Electric AE-SW Series Instruction Manual

Hide thumbs Also See for AE-SW Series:
Table of Contents

Advertisement

Wiring diagram

* The wiring diagram below shows a fully equipped model.
L1
L2
L3
Breaker
Main circuit
Terminal description
13
14
~
53
54
11
12
~
51
52
U1
U2
413
414
D1
D2
DT1
DT2
A1
A2
C1
C2
97
98
P1
P2
P4
RS1
RS2
513
524
513
534
513
544
513
554
513
564
513
574
Z1
Z2
N1
N2
Extension terminals
E-32
N
Terminals for extension
RS1
Electronic trip relay
(ETR)
N1 N2 Z1 Z2
(
)
M8
NCT
ZCT
screw
※Voltage forbid to
be applied.
Dielectric test forbidden
Electronic trip relay
Auxiliary switch "a"
Auxiliary switch "b"
Motor charging
Charged signal (Normal open)
Voltage Input terminal of UVT
Trip terminal of UVT (Remote trip)
Closing coil
Shunt trip
OCR alarm
Power supply for ETR
FG of power supply (FG:Frame Ground)
Alarm reset (Trip cause LED, alarm contact)
Alarm contact for LTD Trip
Alarm contact for STD or INST Trips
Alarm contact for Ground fault, Earth leakage trips or 2nd Pre-alarm contact
Pre-alarm contact
Temperature alarm contact
Error alarm contact
For external ZCT
For Neutral CT
For external display DP2
For Interface unit
For VT unit
Control power supply
Wiring length
2 m or less
RS2
513
P1
P2
Reset circuit
Power supply circuit
Alarm contacts
(Power supply type P3 ~ P5 only)
P4
574 564 554 544 534 524
FG
Control power supply circuit/
alarm contact
Fig. 32
See the gure
below for wiring.
97
C1
A1
D2 D1 413 U1
SHT
CC
UVT
98 C2 A2
DT2 DT1 414 U2
Shorting
bar
Push button
for tripping
Wiring length
2 m or less
OCR
Electric operation circuit
alarm
Accessory Symbols
SHT
Shunt tripping device
CC
Closing coil
M
Motor(Motor charging device)
UVT
UVT coil
AX
Auxiliary switch
AL
OCR alarm switch
CLS
Charge limit switch
SBC
Shorting b-contact
CL
Cell switch
Internal wiring
External wiring (user's wiring)
Control circuit connecter (drawout type)
M

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents