Characteristics setting for the WS type
1
2
Note) The figure shows a model with an optional
G1 setting module, a display, and an MCR switch.
Table 23
No.
Setting item
Symbol
①
Rated current
Ir
②
Uninterrupted current
Iu
③
LTD time
T
L
④
STD pick-up current
Isd
⑤
STD time
Tsd
AE630-SW ~ AE1600-SW
AE2000-SW ~ AE3200-SW, AE4000-SW
INST/MCR
AE2000-SWA, AE4000-SWA
⑥
Ii
pick-up current
AE5000-SW
AE6300-SW
⑦
Pre-alarm current
Ip
⑧
Pre-alarm time
Tp
Remark (1) For WS relay, Pre-alarm current "OVER" setting is lu x 1.15.
Remark (2) The table shows data obtained on the breakers provided with MCR (optional).
Systematic diagram of setting dial coordination
In (CT rating)
Ir
Iu
Ip
Isd
Ip2 (P.29)
Ii
Load current LED (60, 80, 100%, OVER)
Ig (P.28)
6
3
5
4
7
Characteristic setting range
0.5 to 1.0 (0.05 step) x In (CT rating)
0.8 to 1.0 x Ir (0.02 step), pick-up current: 1.15 x Iu
12-25-50-100-150s at Iu x 2
1.5-2-2.5-3-4-5-6-7-8-9-10 x Ir
0.5-0.4-0.3-0.2-0.1-0.06- 0.06-0.1-0.2-0.3-0.4-0.5s
(I
2
t ON)
16-12-10-8-6-4-2-2-4-6-8-10-12-16
12-10-8-6-4-2-2-4-6-8-10-12
(INST)
10-8-6-4-2-2-4-6-8-10
(INST)
Iu x 0.68 to 1.0 (0.04 step)-OVER
1/2 T
at Iu x 2 (PAL contact output after passing 1/2 of T
L
⑦
Pre-alarm
current: Ip
②
Uninterrupted
current: Iu
④
STD pick-up
current: Isd
⑤
STD time: Tsd
I
2
t ON
(ramp)
I
2
t OFF
⑥
INST/MCR pick-up
Current (%)
1.05 x Iu ..... Pick up not performed
1.25 x Iu ..... Pick up performed
(I
2
t OFF)
at Isd x 1.5
when the time set at 0.06s.
x Ir
(INST)
(MCR)
WS1
x Ir
(MCR)
WS2
x Ir
(MCR)
WS3
)
L
③
LTD time: TL
⑧
Pre-alarm
time: Tp
With MCR
Max. breaking time
(In case of AE4000-SW~
current: Ii
6300-SW, it is 0.05s)
Factory
Accuracy
default value
—
1.0
1.0
±20%
150
±15%
10
±20%
It operates in the range
0.5 (I
t ON)
2
between 0.04 and 0.08s
WS1...16 (INST)
±15%
WS2...12 (INST)
WS3...10 (INST)
±10%
OVER
±20%
−
E-23