Technical Data; Heat Pump Water Side Inversion [ ° ] - AERMEC WRL 200 Technical Manual

Water/water chiller
Hide thumbs Also See for WRL 200:
Table of Contents

Advertisement

7.

TECHNICAL DATA

7.1.
HEAT PUMP WATER SIDE INVERSION [ ° ]
Mod. WRL
Cooling capacity
[1]
Input power
Evaporator water flow
Evaporator pressure drop
Condenser water flow
Condenser pressure drop
Heating capacity
[2]
Input power
Condenser water flow
Condenser pressure drop
Evaporator water flow
Evaporator pressure drop
ENERGY INDEXES
EER
COP
AHRI PART LOAD RATINGS
IPLV
EER (100% load)
EER (75% load)
EER (50% load)
EER (25% load)
ELECTRICAL DATA (230V-3-60Hz power supply "6")
Input current (cooling)
Input current (heating)
No pump version
LRA
MCA
MOP
Recommended fuse
Only evaporator pump
LRA
MCA
MOP
Recommended fuse
Only condenser pump
LRA
MCA
MOP
Recommended fuse
Evap + cond pumps
LRA
MCA
MOP
Recommended fuse
Reference data (AHRI standard):
In cooling operation [1]:
Evaporator:
Water outlet temperature ............................6,7°C - 44°F
Water flow .................................................... 0,043l/s per kW - 2,4gpm/ton
∆t .................................................................. 5,56K
Condenser:
Water inlet temperature ..............................29,4°C - 85°F
Water flow .................................................... 0,054l/s per kW - 3gmp/ton
∆t .................................................................. 5,31K
IWRLPY. 1403. 5890710_01
10
U.M.
200
400
ton
15,26
20,64
kW
11,38
15,08
gpm
36,56
49,43
PSI
3,1
5,5
gpm
45,99
61,97
PSI
4,2
8,2
BTU/h
198652
267625
kW
14,11
19,1
gpm
44,09
59,40
PSI
3,9
7,5
gpm
33,94
45,66
PSI
2,7
4,7
BTU/W
16,12
16,44
W/W
4,13
4,11
W/W
21,06
21,47
W/W
4,72
4,81
W/W
5,60
5,71
W/W
6,63
6,76
W/W
6,54
6,67
A
42
53
A
47
62
A
222
276
A
69
84
A
100
121
A
90
110
A
230
284
A
77
91
A
108
129
A
100
125
A
230
284
A
77
91
A
108
129
A
100
125
A
237
292
A
85
99
A
115
136
A
110
125
500
26,86
19,02
64,33
3,0
80,25
3,9
344456
23,4
76,45
3,6
59,61
2,6
16,96
4,31
22,16
4,97
5,89
6,97
6,88
71
83
357
129
186
175
365
136
194
175
365
136
194
175
373
144
201
200
In heating operation [2]:
Evaporator:
Water inlet temperature ..............................10°C - 50°F
Water outlet temperature ............................5°C - 41°F
∆t .................................................................. 5K
Condenser:
Water inlet temperature ..............................40°C - 104°F
Water outlet temperature ............................45°C - 113°F
∆t .................................................................. 5K