STORAGE

STORAGE
It may happen that, after receipt, the units are not to be immediately installed and are kept in storage. In case of medium-long term storage, we recommend ap-
plying the following procedures:
• Make sure there is no water inside the hydraulic systems.
• Do not remove the protections from the heat exchanger.
• Do not remove the plastic protective films.
• Make sure that the electrical panels are closed.
• Before using the equipment, store all items provided in a dry and clean place so that they can be used in the future. We recommend storing the unit in a dry and
sheltered place (especially for units intended for indoors).
NOTE The maximum storage temperature of the units depends on the type of refrigerant contained, see table. Beyond this limit, there is a risk of refrigerant leaking
through the safety valves.
Maximum storage temperature
Refrigerant
R134a
R410A
R1234ze
R513A
PLACEMENT AND INSTALLATION REQUIREMENTS
For unit installation it is important to perform the following preliminary
preparation tasks:
• When installing, make sure that the atmospheric or environmental agents do
not affect and corrode the cooling circuit components, causing the refrigerant
to leak in the environment and, if so, make the appropriate adjustments.
• The air-cooled units with fans are designed for outdoor installation. Contact
Aermec before making any type of installation.
• The water-cooled units are designed for indoor installation. Contact Aermec
before making any type of installation.
• For the positioning of the air-cooled units for outdoor use, choose a place that
is not exposed to excessive wind (install windbreaks if the wind speed exceeds
86.6 in/s).
• The soil under the unit must be flat, smooth and sufficiently strong to
withstand the weight of the unit with a full refrigerant load, as well as the
occasional presence of the normal maintenance equipment.
• In locations exposed to frost, if the unit is installed on soil, the support base
must rest on concrete columns with a depth greater than the normal depth of
frost of the soil. It is always advisable to build a support base separate from the
main building to avoid the transmission of vibrations.
• Stationary appliance: for normal applications, the rigidity of the unit and the
positioning of point loads allow for an installation that minimises vibrations. In
the case of installations requiring particularly low vibration levels, you can use
the anti-vibration supports.

MINIMUM TECHNICAL SPACES

B1
B2
Type
HFC
HFC
HFO
HFO
A1
C2
C1
Class
A1
A1
A2L
A1
ATTENTION: The use of anti-vibration supports MUST be combined with the
installation in the unit water piping of flexible couplings. The anti-vibration
supports must be fixed to the unit BEFORE it is earthed. AERMEC is not
responsible for the choice of capacity of the anti-vibration supports.
• For installation on vibration dampers:
The unit must be fixed to the anti-vibration supports and these firmly fixed
to the concrete base, see chapter weight distribution and minimum technical
spaces
• For installation without vibration dampers: fix the unit to the base using
screws with the necessary resistance
• Check that the contact surfaces of the anti-vibration supports are levelled to
the base. If necessary, use spacers or level the base but, in any case, make sure
that the anti-vibration supports rest flat on the base surface.
• It is essential that the units are installed leaving sufficient space around them
to allow easy access to the components for maintenance and repair purposes.
• Unit for installation at max. 2000m a.s.l.
ATTENTION: It is important that the units are installed flat. The improper
installation of the unit invalidates the warranty.
This is an appliance not accessible to the general public.
Maximum temperature in technical rooms
Unit for internal installation.
Protection rating: IP X0
The unit has to be installed
in technical rooms, in
accordance with current
regulations at the place of
installation
ATTENTION:
DRAWINGS ONLY
INDICATIVE
Unit
Sizes
A1
in
WRL / WRL -H 200-400-500
23.6
Max. Temp. (°C)
<122°F
<122°F
<122°F
<122°F
°F
104
B1
B2
C1
in
in
in
23.6
23.6
23.6
C2
in
23.6
9