Sound Data; Sound Level Of Wrl Standard Version; Safety And Ceck Parameter Settings - AERMEC WRL 200 Technical Manual

Water/water chiller
Hide thumbs Also See for WRL 200:
Table of Contents

Advertisement

15.

SOUND DATA

15.1.
SOUND LEVEL OF WRL STANDARD
VERSION
SOUND POWER:
Aermec determines sound power values on the
basis of measurements made in accordance
with UNI EN ISO 9614-2, as required for Euro-
vent certification.
SOUND PRESSURE:
Sound pressure in free field, at 10 m/ 393,7in
distance from the external surface of the unit
(in accordance with UNI EN ISO 3744)
16.
SAFETY AND CECK PARAMETER
SETTINGS
IWRLPY. 1403. 5890710_01
22
Sound pressure dB(A)
Sound power
WRL
dB(A)
32,8ft
WRL 200
78
46
WRL 400
82
50
WRL 500
83
51
Reference data (AHRI standard) in cooling operation:
EVAPORATOR
Water outlet temperature ..... 6,7°C - 44°F
Water flow ............................. 0,043l/s per kW - 2,4gpm/ton
CONDENSER
Water inlet temperature ....... 29,4°C - 85°F
Water flow ............................. 0,054l/s per kW - 3gpm/ton
CHECK PARAMETERS
Water inlet temperature in cooling mode.
Cold Setting
Water inlet temperature in heat mode.
Heating Setting
Anti-freeze
Intervention temperature for the anti-freeze
intervention
alarm, on EV side (water outlet temperature).
Proportional temperature band within which
Total differential
the compressors are activated and deactiva-
ted.
Compressor thermomagnetic
Power supply: 230/3/60
MTC1
MTC2
Power supply: 460/3/60
MTC1
MTC2
Power supply: 575/3/60
MTC1
MTC2
Transducers and pressure switches
High pressure switch (HP)
High pressure transducer (THP)
Low pressure transducer (TLP)
Refrigerant circuit safety
High pressure relief valve
Sound power by central band freq. dB(A)
3,3ft
125
250
500
61
64,2
60,7
63,9
65
77,6
73,5
68,9
66
65,9
74,4
73,2
u.m.
WRL 200
WRL 400
A
34
A
34
A
16
A
16
A
12
A
12
u.m.
WRL 200
WRL 400
bar/PSI
40/580,2
40/580,2
bar/PSI
39/565,6
39/565,6
bar/PSI
1,6/23,2
1,6/23,2
u.m.
WRL 200
WRL 400
bar/PSI
40,5/587,4
40,5/587,4
1000
2000
4000
8000
69,1
75,3
71,6
51,6
65,1
75,3
74,8
62,5
72,5
74,2
80,1
60,5
5°C/41°F
MIN.
20°C/68°F
MAX.
12°C/53,6°F
DEFAULT
MIN.
20°C/68°F
55°C/131°F
MAX.
38°C/100,4°F
DEFAULT
MIN.
-
-
MAX.
4°C/39,2°F
DEFAULT
MIN.
0°C/32°F
15°C/59°F
MAX.
4°C/39,2°F
DEFAULT
WRL 500
41
63
41
63
22
28
22
28
16
24
16
24
WRL 500
40/580,2
39/565,6
1,6/23,2
WRL 500
40,5/587,4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wrl 400Wrl 500

Table of Contents