Quick reference
for setting
Channel
Code Event
8...17
E1
Input channel activated
8...17
E2
Input channel reset
8...17
E3
SIGNAL5 or 6 output activated
8...17
E4
SIGNAL5 or 6 output reset
0
E50
Restarting
0
E51
Overflow of event register
0
E52
Temporary disturbance in data
communication
0
E53
No response from the module
over the data communication
0
E54
The module responds again
over the data communication
0 not included in the event reporting
1 included in the event reporting
* no code number
- cannot be set
In the SPACOM system the event codes
E52...E54 are generated by the substation level
control data communicator.
1) No event codes E5...E8 are obtained if the
outputs are controlled by the Direct Output
Control function.
2) Event E9, output activation inhibited, is
obtained if the operation is inhibited by the
interlocking program or by an input channel
8...17.
If all the parameters are set at the same time, you
should follow the instructions below when
changing between setting and run mode and
when storing the parameters.
The default values of the parameters relating to
interlocking and configuration are:
S100 = 0
Freely selectable configuration and inter-
locking system
S198 = 0
The interlocking program is in setting mode
S199 = 1
Interlockings are in use
The following example shows the setting proce-
dure.
Number
representing
the event
1
2
4
8
*
*
*
*
3) Event E10, open or close command failed, is
obtained if the status of the controlled object
does not change within the time of the
output pulse.
4) Event E11, attempt to activate an output
without open/close selection is obtained when
a secured control is made in a situation where
the state of alert has not been defined.
Example 21:
To select a user-specific configuration and inter-
locking system.
>99WS198:0:XX
; Change into setting mode
>99WS100:0:XX
; Change into freely selectable mode
>99WS101:...
; Configuration commands
:
>99WM200:...
; Interlocking program
:
>99WS198:1:XX
; Change into run mode
:
Other parameters
:
>99WV151:1:XX
; Store set parametres
Default value
of the event
factor
1
1
0
0
V155 = 3
-
-
-
-
-
33