ABB SPAC 531 C User Manual And Technical Description page 19

Feeder terminal
Table of Contents

Advertisement

The switches of the programming switchgroup
SGB on the PC boards of the overcurrent and
earth-fault modules are used for linking the
starting signals of the relay modules to the
starting inputs of the auto-reclose module. The
SGB switches are also used for connecting the
incoming blocking signals to the protection.
Switch
Function
SGB/1
Links the starting signal of stage I> to the starting input AR2 of the
auto-reclose module. (generally the starting input of AR initiated by
the low-set overcurrent stage)
SGB/2
Links the starting signal of stage I>> to the starting input AR2 of the
auto-reclose module
SGB/3
Links the starting signal of stage I>> to the starting input AR1 of the
auto-reclose function. (generally the starting input of AR initiated by
the high-set overcurrent stage)
SGB/4
Forms from the blocking input signal BS1 a blocking signal for the
tripping of stage I>
SGB/5
Forms from the blocking input signal BS1 a blocking signal for the
tripping of stage I>>
SGB/6
Forms from the blocking input signal BS2 a blocking signal for the
tripping of stage I>
SGB/7
Forms from the blocking input signal BS2 a blocking signal for the
tripping of stage I>>
SGB/8
No function in SPAC 531/631 C. Has to be in position 0
Note!
Only one of the switches SGB/2 and SGB/3 is
allowed to be in position 1.
The SGB switches on the PC board of the
overcurrent module SPCJ 3C3 have the follow-
ing functions:
Default
value
1
0
1
0
0
0
0
0
19