ABB SPAC 531 C User Manual And Technical Description page 122

Feeder terminal
Table of Contents

Advertisement

Remote transfer
data
20
Apart from the event codes the control data
communicator is able to read, over the SPA bus,
all input data (I data) of the relay module, set
values (S values), output status data (O data)
information recorded in the memory (V data),
Data
Current on phase L1 as a multiple
of the rated current
Current on phase L2 as a multiple
of the rated current
Current on phase L3 as a multiple
of the rated current
Blocking of tripping of stage I>
Blocking of tripping of stage I>>
Starting of stage I>
Tripping of stage I>
Starting of stage I>>
Tripping of stage I>>
Alerted start value for stage I>
Alerted operation time for stage I>
or time multiplier k
Alerted start value for stage I>>
Alerted operation time for stage I>>
Alerted checksum of switchgroup SG1
Start value of stage I>, set with
the setting knob
Operation time or time multiplier of
stage I>, set with the setting knob
Start value of stage I>>, set with
the setting knob
Operation time of stage I>>, set
with the setting knob
Checksum of switchgroup SG1,
set with the switches
Remote setting percentage of the
start value of stage I>
Remote setting percentage of the
operation time or time multiplier
of stage I>
Remote setting percentage of the
start value of stage I>>
Remote setting percentage of the
operation time of stage I>>
Remotely set checksum for the
switchgroup SG1
and some other data. Further, part of the data
can be altered by commands given over the SPA
bus. Any information is located on channel 0,
which needs not to be written in the data com-
munication instructions.
Code
Data
Values
direct.
I1
R
0...63 x I
I2
R
0...63 x I
I3
R
0...63 x I
I4
R
0 = no blocking
1 = tripping of stage I> blocked
I5
R
0 = no blocking
1 = tripping of stage I>> blocked
O1
R
0 = stage I> has not started
1 = stage I> started
O2
R
0 = stage I> not tripped
1 = stage I> tripped
O3
R
0 = stage I>> not started
1 = stage I>> started
O4
R
0 = stage I>> not tripped
1 = stage I>> tripped
S1
R
0.5...2.5 x I
S2
R
0.05...100 s
0.05...1.00
S3
R
0.5...20 x I
999 = ∞, infinite
S4
R
0.04...100 s
S5
R
0...255
S11
R
0.5...2.5 x I
S12
R
0.05...100 s
0.05...1.00
S13
R
0.5...20 x I
999 = ∞, infinite
S14
R
0.04...100 s
S15
R
0...255
S21
R, W
0...999%
S22
R, W
0...999%
S23
R, W
0...999%
S24
R, W
0...999%
S25
R, W
0...255
n
n
n
n
n
n
n