ABB SPAC 531 C User Manual And Technical Description page 41

Feeder terminal
Table of Contents

Advertisement

External auto-reclose start input (input channel 14)
Terminal numbers
Control voltage range
- I/O module type SPTR 4D1
- I/O module type SPTR 4D2
Current drain
Contact outputs
Control outputs
- rated voltage
- continuous carry
- make and carry for 0.5 s
- make and carry for 3 s
- breaking capacity for dc, when the control circuit
time constant L/R≤ 40 ms at the control voltage
levels 48/110/220 V dc
- contact material
- operating principle when controlled by the
control module
Signal outputs
- rated voltage
- continuous carry
- make and carry for 0.5 s
- make and carry for 3 s
- breaking capacity for dc, when the control circuit
time constant L/R≤ 40 ms at the control voltage
levels 48/110/220 V dc
- contact material
Auxiliary supply voltage
Built-in power supply module type and
permitted supply voltage range
- type SPGU 240A1
- type SPGU 48B2
Burden of auxiliary supply under quiescent/
operating conditions
Overcurrent module SPCJ 3C3
Low-set overcurrent stage I>
- starting current I>, setting range
- operation modes to be selected
- definite time operation
- operate time t>
- inverse definite minimum time (IDMT) mode
acc. to IEC 255-4 and BS 142
- time multiplier k
High-set overcurrent stage I>>
- starting current I>>, setting range
- operate time t>>
X5/9-10
80...265 V dc
30...80 V dc
~2 mA
X1/3-4, 6-7,
X3/11-12, 13-14, 15-16, 17-18,
X4/11-12, 13-14, 15-16, 17-18,
X5/11-12, 13-14, 15-16, 17-18
250 V ac or dc
5 A
30 A
15 A
5 A/3 A/1 A
AgCdO
2
pulse, pulse length 0.1...100 s
X1/8-9-10,
X2/1-2-3, 4-5-6, 7-8-9,
X6/1-2, 3-4
250 V ac or dc
5 A
10 A
8 A
1 A/0.25 A/0.15 A
AgCdO
2
80...265 V ac or dc
18...80 V dc
~15 W / ~20 W
0.5...2.5 x I
n
0.05...100 s
Extremely inverse
Very inverse
Normal inverse
Long-time inverse
0.05...1.00
and ∞
0.5...20 x I
n
0.04...100 s
41