Example 2:
To configure five objects (indicators 101, 109
and 103 for disconnectors, indicator 102 for a
>99WS198:0:XX
>99WS100:0:XX
>99WS101:1,1,1,20,0:XX ; Disconnector 1: vertical red LEDs indicate closed status
>99WS109:1,1,2,22,0:XX ; Disconnector 2: vertical red LEDs indicate closed status
>99WS102:1,1,3,24,1:XX ; Circuit breaker:
>99WS103:1,1,4,0,0:XX
>99WS108:1,0,5,0,0:XX
>99WV151:1:XX
After this the interlocking program has to be
written before it is possible to open or close the
circuit breaker and the disconnectors. See Chap-
ter "Interlocking".
Fig. 7. Object configuration set in example 2.
circuit breaker and indicator 108 for an earth
switch), the following commands are required:
; Enter into setting mode
; Enter into mode for free configuration
for input channel 1.
Control outputs OPEN1 and CLOSE1
for input channel 2.
Control outputs OPEN2 and CLOSE2
vertical red LEDs indicate closed status
for input channel 3.
Controloutputs OPEN3 and CLOSE3
; Disconnector 3: vertical red LEDs indicate closed status
for input channel 4.
No control
; Earthing switch: horizontal red LEDs indicate closed status
for input channel 5.
No control
; Store the set parameters
The selected configuration can be read indicator
by indicator or all together with one single
instruction.
Example 3:
Reading the configurations of indicators 101...
116 by using one single instruction.
>99RS101/116:XX
This instruction will give the setting values of
each indicator (101 to 116 ), including those not
configured into the system. The parameter val-
ues of the indicators not in use are zero.