ABB SPAC 531 C User Manual And Technical Description page 31

Feeder terminal
Table of Contents

Advertisement

The contact functions are the same as those in
example 1. Also the SG1 switches on the front
plate can be set as in example 1. When the SGB
switches on the PC boards and the SGR switches
of the I/O module are set as above and the
parameters of the control module SPTO 6D3 in
accordance with the table below, all auto-reclose
Parameter
Value
S78
1
S21
0
S22
1
S23
1
S24
0.0
S25
0.0
S26
0.3
S31
0
S32
0
S33
1
S35
0.0
S36
120
S77
5.0
V151
1
The setting of the AR parameters is described in
detail in the manual for the control module
SPTO 6D3.
Function
Alerts the auto-reclose functions
Prevents AR1 from starting initiated by the high-set phase
overcurrent stage
Starts AR1 initiated by tripping of the overcurrent module
Starts AR1 initiated by tripping of the earth-fault module
Sets AR1 starting time at 0.0 s, AR initiated by tripping of the
overcurrent module
Sets AR1 starting time at 0.0 s, AR initiated by tripping of the
earth-fault module
Sets AR1 dead time at 0.3 s
Prevents starting of AR2 initiated by tripping of the high-set stage
of the overcurrent module
Does not start AR2 initiated by tripping of the overcurrent module
Starts AR2 initiated by tripping of the earth-fault module
Sets AR2 starting time at 0.0 s, AR initiated by earth-fault module
Sets AR2 dead time at 120 s
Sets the reclaim time at 5.0 s
Stores the input parameters
functions will be blocked by the high-set stage.
The tripping signal from the low-set stage of the
phase overcurrent module will start a HSAR
sequence and the tripping signal from the neu-
tral overcurrent module both a HSAR and a
DAR sequence.