Sullair DE-18 Series Operator's Manual And Parts List page 31

Oil-free air compressor 1500 cfm
Hide thumbs Also See for DE-18 Series:
Table of Contents

Advertisement

Table 5-2 Controller Responses
CLASS
SD/WA
B
WA
A
SD
S
SD
S
SD
A
SD
A
SD
A
SD
A
SD
A
SD
A
SD
A
SD
A
SD
S
AL
S
AL
S
AL
S
AL
S
AL
S
AL
S
AL
S
AL
S
AL
"A" always armed "B" armed when the lockout delay timer expires
"S" armed when its own lockout delay timer expires
When a shutdown or warning condition exists, the reset button must be pressed to clear and reset the system.
In the case of a warning, when the reset push button is pressed, if the warning condition has already cleared
itself, then the warning display and compressor warning/shutdown light will be cleared. If the warning condi-
tion is still present, then the warning display and the compressor warning /shutdown light will remain on. In
the case of a shutdown, the unit will be locked out from running or being restarted until the reset push button
is pressed. Once the reset push button is pressed, and the shutdown condition has been cleared, the com-
pressor warning/shutdown light will be turned off, and the unit will go into "STANDBY" mode to be ready to
start.
EMS DISPLAY
CAT ECM DIAGNSTC
CAT SD
C267 COMM FAIL
MDDM COMM FAIL
LST ANLG P1 SD
LST ANLG P2 SD
LST ANLG P3 SD
LST ANLG P4 SD
LST ANLG T1 SD
LST ANLG T2 SD
LST ANLG T3 SD
LST ANLG T4 SD
S #1 COM
S #2 COM
S #3COM
S #4 COM
S #5 COM
S #6 COM
S #7 COM
S #8 COM
S #9 COM
CONTROLLER
SET POINT
ON
ON
lost signal
lost signal
trip point fixed @<0.63V or 32 counts. Pressure
transducer or connection failure
trip point fixed @<0.63V or 32 counts. Pressure
transducer or connection failure
trip point fixed @<0.63V or 32 counts. Pressure
transducer or connection failure
trip point fixed @<0.63V or 32 counts. Pressure
transducer or connection failure
trip point fixed @<2.5 ma or 32 counts. Temperature
sensor or connection failure
trip point fixed @<2.5 ma or 32 counts. Temperature
sensor or connection failure
trip point fixed @<2.5 ma or 32 counts. Temperature
sensor or connection failure
trip point fixed @<2.5 ma or 32 counts. Temperature
sensor or connection failure
slave #1 communication failure
slave #2 communication failure
slave #3 communication failure
slave #4 communication failure
slave #5 communication failure
slave #6 communication failure
slave #7 communication failure
slave #8 communication failure
slave #9 communication failure