Advertisement

Note
Shielding is not required if at least one of the following conditions is satisfied:
• The cables must not be longer than 1 m.
• The cables are routed flush with the rear metal panel of the control cabinet.
• In the control cabinet, the cables are routed separately from the signal cables.
6.2.2.2

Shield support with optional shield connection plate

Only use shielded connecting cables with the optional shield connection plate. It is
recommended that the cable is additionally fastened to the strain relief plate.
Figure 6-7
Table 6-15
Designation
Optional shield connection plate
Booksize power units
Equipment Manual, 01/2022, 6SL3097-6AC30-0BP0
Screws for fastening the strain relief plate
Strain relief plate
Screws for fastening the optional shield connection plate
Optional shield connection plate with fastening for the shield connection clamp
Shield support for Smart Line Modules
Optional shield connection plate
6.2 Accessories for Smart Line Modules
Article number
6SL5166-1BD00-0AA0
Accessories
Tightening torque for
3 Nm (26.6 lbf in)
97