4.5.3
Interface description
Overview
You can use either the upper or lower screw to connect the protective conductor. One of the
screws remains unused. "Looping-through" the protective connection to the line reactor is not
permissible.
Line and load connections
Table 4-3
Line and load connections, Basic Line Filter for Smart Line Modules
Article number
Rated power [kW]
Line connection
L1, L2, L3
Load connection
L1´, L2´, L3´
Protective conductor connection
1)
For ring cable lugs without insulation
The maximum cable length between line filter and line reactor and between line reactor and
Smart Line Module is 10 m.
Booksize power units
Equipment Manual, 01/2022, 6SL3097-6AC30-0BP0
6SL5100-
0HE21-6DD0
16
Screw terminals 6 ... 16 mm
(AWG 6 ... AWG 10), 3-pin
2.0 ... 2.2 Nm (17.7 ... 19.5 lbf in)
M8 5.7 ... 6.3 Nm (55.7 lbf in)
1)
Line connection and line-side power components
①
Protective conductor
②
Load connection
③
Protective conductor
④
Line connection
0HE22-4DD0
24
Screw terminals 6 ... 16 mm
2
(AWG 6 ... AWG 10), 3-pin
2.0 ... 2.2 Nm (17.7 ... 19.5 lbf in)
M8 5.7 ... 6.3 Nm (55.7 lbf in)
4.5 Line filters
2
47