Specifications - Baso C610U Series Manual

24 vac universal intermittent pilot gas ignition contro

Advertisement

SPECIFICATIONS

Input Voltage
Input Current
Gas Valve Contact Rating
Alarm Output
Operating Temperature
Flame Detection Means
Flame Detection Type
Minimum Flame Current
Flame Failure Response Time
Ignition Source
Maximum spark Gap
High Voltage Cable
Flame Sense Cable
Spark
Humidity
Gas Types
Trials Before 100% Shutoff *
Trial for Ignition Time *
Pre-Purge Time *
Inter-Purge Time *
Retry Delay Period *, **
Lockout Recovery
*32 Selectable preset timings via. 5 position DIP Switch.
**Retry is not available in CE ignitions.
AGENCY CERIFICATIONS
UL 60370-1, UL 60730-2-5
EN298:2012
©
2018 BASO Gas Products
Part No. BASO-INS-C610UQRG, Rev. C
24 VAC Universal Intermittent Pilot Gas Ignition Control
Control: 24 VAC(18-30 VAC) 50/60 Hz
0.3 A nominal + valves
2A pilot and 2A Main @ 24 VAC
.2A @ 24 VAC
-40 to 176°F (-40 to 80°C)
Flame Rectification
Local/Internal or Remote/External
0.07 microamperes
1.0 second maximum
High voltage spark, capacitive discharge
0.2 in. (5.1 mm)
48 in. (1219 mm) max., rated 15kV min.
(Resistive recommended)
48 in. (1219 mm) max., rated 15kV min.
(Shielded recommended)
30 sparks/second
0% to 95% RH (non-condensing)
Natural, LP, or Manufactured
Preset 1, 3, Cont.
Preset 4, 8, 15, 30, 50, 60, 90, 120, 240 seconds
Preset 0, 15, 30 or 45 seconds
Preset 0, 15, or 300 seconds
Preset 0, 5, or 60 minutes
Power cycle / Thermostat (TH-W) cycle
File: M2926 Software conforms to UL60730
Requirement Component Recognized System
(US & Canada)
File: 657989
2
www.baso.com

Advertisement