(DSI) modules, including those manufactured by Honeywell, Robert Shaw, ICM, Fenwal, and Johnson Controls. The following is an overview of the C107U series control, and is intended to only be used by Certified Service Technicians. APPLICATION •...
SETUP AND ADJUSTMENTS DIP Switch (S1) Settings When replacing an existing ignition control with the C107U, refer to Table 2 for the correct DIP switch settings. For a complete list of the controls the C107U replaces, see the BASO C107U Installation Instructions available at www.baso.com.
(13mm) in the flame. See Figure 1. • Dirty or corroded flame sensor • Faulty flame sensor wiring • Poor burner ground Note: For more information on BASO ignitions and other products, plus complete installation instructions, please visit us at www.baso.com. CORRECT FLAME TOO LOW...
Page 8
Figure 2: Microammeter Connection. Important: Preventative maintenance programs are an important part of maintaining optimum and safe function of you BASO Products. Any attempt to repair this assembly voids the manufacturer's 2-year warranty. For a replacement control, contact the original equipment manufacturer or nearest BASO Gas Products distributer.