Troubleshooting Guide - Baso C610U Series Manual

24 vac universal intermittent pilot gas ignition contro

Advertisement

TROUBLESHOOTING GUIDE

1. No power up
 Faulty 24 VAC wiring
 Thermostat or transformer
 Faulty control
 Safety limits
2. Control LED is blinking RED
 Determine error code, refer to error codes (TABLE 5), also
refer to the troubleshooting flow chart in the installation
instructions
3. No spark during Trial for Ignition (TFI) time
 Faulty spark electrode wiring
 Spark gap too wide
 Faulty control
4. Pilot/Burner does not light during trial for ignition time
 Faulty valve wiring
 Bad Gas Valve
 Faulty Control
5. Burner lights but gas valve turns off after TFI
 Weak flame, flame not in contact with the spark electrode of
flame sensor. Check that flame sensor tip is in the flame.
For proper sensing, the rod tip must be 3/8" (10mm) to 1/2"
(13mm) in the flame. See figure 1.
 Dirty or corroded flame sensor
 Faulty flame sensor wiring
 Poor burner ground
Note: For more information on BASO ignitions and other products, plus
complete installation instructions, please visit us at www.baso.com.
Figure 1: Proper Flame Sensor Position
©
2018 BASO Gas Products
Part No. BASO-INS-C610UQRG, Rev. C
CORRECT
24 VAC Universal Intermittent Pilot Gas Ignition Control
FLAME TOO LOW
FLAME TOO HIGH
www.baso.com