Download Print this page

Specifications - Baso C107U Quick Reference Manual

Advertisement

SPECIFICATIONS

Input Voltage
Input Current
Gas Valve Contact Rating
Alarm Output
Operating Temperature
Flame Detection Means
Flame Detection Type
Minimum Flame Current
Flame Failure Response Time
Ignition Source
Maximum Spark Gap
High Voltage Cable
Flame Sense Cable
Spark
Humidity
Gas Types
Trials Before Lockout *
Trial for Ignition (TFI) Time*
Pre-Purge Time *
Inter-Purge Time *
Retry Delay Period *, **
Lockout Recovery
*32 Selectable preset timings via. 5 position DIP Switch.
**Retry is not available in CE ignitions.
Agency Certifications
©
2019 BASO Gas Products
Part No. BASO-INS-C107UQRG, Rev. C
UL 60370-1, UL 60730-2-5
EN298:2012
24 VAC Universa Direct Spark Gas Ignition Control
Control: 24 VAC (18-30 VAC) 50/60 Hz
0.3 A nominal + valves
4A Main @ 24 VAC
2QA @ 24 VAC
-40 to 176°F (-40 to 80°C)
Flame Rectification
Local/Internal or Remote/External
0.07 microamperes
1.0 second maximum
High voltage spark, capacitive discharge
0.2 in. (5.1 mm)
48 in. (1219 mm) max., rated 15kV min.
(Resistive recommended)
48 in. (1219 mm) max., rated 15kV min.
(Shielded recommended)
30 sparks/second
0% to 95% RH (non-condensing)
Natural, LP, or Manufactured
Default, 1, or 3
Default, 4, 7, 11, or 21 seconds
Default, 0, or 30 seconds
Default, 0, 15, 30, or 90 seconds
Default, 0, 5*, or 60* minutes
Power cycle
File: M2926 Software conforms to UL60730
Requirement Component Recognized System
(US & Canada)
File: 657989
2
www.baso.com