WARNING
Supply the unit at least 24 hours before the initial startup to heat the compressor oil. In conditions of
low water temperature, the pumps could be started in order to avoid freezing conditions. In order to
avoid the breaking of heat exchangers due to water hammer, be sure to keep to water valves open.
Failure to follow these instructions will void the warranty.

Advanced electronics

The control logic is able to manage air/water and water/water chillers, chillers with total recovery and
heat pump versions.
This control logic, according the type of the unit, is able to handle multi scroll units and screw units
with a proportional step regulation according inlet water temperature or proportional + integral regula-
tion according leaving water temperature.
.