easy-Drive 200L
March 2022
Calibrate Travel of the Actuator to the Valve Assembly
Step 13.Ensure the process and valve are in a safe
state – the valve will move during the
calibration steps.
Step 15.Press the "Calibrate Span" button to
initiate the span calibration. The software
will show a progress bar during the
calibration and display "Valve Span
Calibrated" when complete.
Step 17.Verify full desired travel is achieved when
commanded to 100% by confirming
"Actual Position" in the Configurator is
100%.
Note
If actuator cannot achieve desired travel, review steps 5-12 to ensure all steps were followed, validate proper Configurator
selections were made, and confirm the stems were properly coupled.
The valve/actuator assembly is now ready to be put into operation. If the 200L is not operating properly contact your
Emerson sales
office.
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher and easy-Drive are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson
Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their
respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay, 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
4
E 2022 Fisher Controls International LLC. All rights reserved.
Step 14.Navigate to the Calibration tab of the
Configurator
Step 16.Verify valve is closed when commanded
to 0%.
Quick Start Guide
D104725X012