Download Print this page

Emerson Fisher easy-Drive 200L Quick Start Manual page 2

Hide thumbs Also See for Fisher easy-Drive 200L:

Advertisement

easy-Drive 200L
March 2022
Ensure Actuator Stem is in the Proper Position Prior
to Mounting and Coupling
Your 200L actuator has internal hard stops to limit maximum travel within the actuator. A new actuator will be shipped
from the factory at 6% off the lower internal hard stop, which is the recommended mounting position.
Note
If you are mounting a new actuator that has never been positioned and is still in its recommended mounting position of 6% of
maximum travel, you can begin at step 5.
To set the stand-alone 200L actuator to the recommended mounting position of 6% of maximum travel, follow steps
1-4:
Step 1. Ensure use of a stand-alone 200L
(must be actuator only, no valve body).
X1520-1
Step 3. Perform Span Calibration from
Calibration tab.
Note
Stop-to-Stop is used for positioning the actuator to 6% off the lower travel stop.
Select proper valve type and travel after mounting the 200L to the valve body.
2
Step 2. Using the Fisher easy-Drive Configurator,
select the "System" tab and then
"Advanced Settings." Select the valve
type "Stop-to-Stop" from the drop-down
options and click "Apply."
Step 4. Position actuator to 6% travel.
Quick Start Guide
D104725X012

Advertisement

loading