This read only holding register allows individual notification of the active problem code. The alarms are not ordered
based on any priority. If multiple problem alarms are present at one time, this object will be set to the alarm that has the
highest alarm code. This object is set to zero if no problem alarms are active.
Data Type
Holding Register
RO Holding Register
32
Problem Alarm Index
Keypad Menu Path No Keypad Equivalent
This read only holding register allows individual notification of the active problem index. The alarms are not ordered
based on any priority. If multiple problem alarms are present at one time, this object will be set to the alarm that has the
highest problem index. This object is set to zero if no problem alarms are active.
Data Type
Holding Register
RO Holding Register
29
Run Enabled
Keypad Menu Path No Keypad Equivalent
This read only holding register indicates the running mode of the chiller. The Run Enabled output data point indicates
that the chiller can start if operating conditions are met.
Data Type
Holding Register
RO Holding Register
3
Units
Keypad Menu Path No Keypad Equivalent
This read/write holding register allows you to select the units that are being passed through Modbus.
Data Type
Holding Register
RW Holding Register
316
Warning Alarm Code
Keypad Menu Path No Keypad Equivalent
This read only holding register allows individual notification of the active warning code. The alarms are not ordered
based on any priority. If multiple warning alarms are present at one time, this object will be set to the alarm that has the
highest alarm code. This object is set to zero if no warning alarms are active.
Data Type
Holding Register
RO Holding Register
31
Warning Alarm Index
Keypad Menu Path No Keypad Equivalent
This read only holding register allows individual notification of the active warning index. The alarms are not ordered
based on any priority. If multiple warning alarms are present at one time, this object will be set to the alarm that has the
highest alarm index. This object is set to zero if no warning alarms are active.
Data Type
Holding Register
RO Holding Register
28
27
Measurement
Units
Active Problem Alarm
N/A
Measurement
Units
Active Warning Alarm
N/A
Measurement
Units
Chiller State
N/A
Measurement
Units
Units of Measure
N/A
Measurement
Units
Active Warning Alarm
N/A
Measurement
Units
Active Warning Alarm
N/A
Valid Range
See the Active Alarms section
on page 29 for details.
Valid Range
See the Active Alarms section
on page 29 for details.
Valid Range
0=Off, 1=RunAllowed
Valid Range
0=English, 1=Metric
Valid Range
See the Active Alarms section
on page 29 for details.
Valid Range
See the Active Alarms section
on page 29 for details.