Introduction; Chiller Models; Controller Data Points - Daikin McQuay MicroTech III Manual

Chiller unit controller protocol information
Table of Contents

Advertisement

Introduction

This document contains the necessary information to incorporate a MicroTech
International into your Building Automation System (BAS). It includes all necessary Modbus® variables and
corresponding MicroTech III Chiller Unit Controller data points. Modbus terms and principles are not defined. Refer to
the appropriate specifications for definitions and details.

Chiller Models

The following table lists the model designators of McQuay International Chiller units and the corresponding description.
AWS
Air-Cooled World Screw

Controller Data Points

The MicroTech III Chiller Unit Controller contains data points or unit variables that are accessible from two different
user interfaces: the unit keypad/display or a Modbus serial network. Not all points are accessible from each interface.
This manual lists all important data points and the corresponding network path for each applicable interface. Refer to the
applicable Operation Manual for keypad/display details.
The MicroTech III Chiller Unit Controller maps additional Modbus registers that are not
included in this document. These registers are for internal use only. Please contact McQuay
Controls Customer Support at 866-462-7829 for assistance with Modbus integration.
5
®
III Chiller Unit Controller from McQuay