Directional Relay Testing; Introduction - ISA T1000 PLUS User Manual

Hide thumbs Also See for T1000 PLUS:
Table of Contents

Advertisement

DOC. MIE91093
1.5 D
IRECTIONAL RELAY TESTING

1.5.1 Introduction

These relays are used to protect MV feeders against Earth
faults by detecting the residual voltage V
I
and the relative angle. Normally the current is lagging; for
o
neutral isolated lines, I
(resistance, Petersen Coil), the phase angle can be less: 40°,
60°. This is also the angle of maximum sensitivity of the relay.
Since relay inputs are one current and one voltage, we'll use I
main and V aux to perform the test.
The parameters that we will test are:
The characteristic angle, sometimes called MTA= max
torque angle (electromagnetic relays), and the Angle
sector, that is half of the operating angle;
The pick up of Io;
The pick up of Vo.
When testing one parameter we have to set the other two at a
value above the pick up.
Test MTA: we keep Vo and Io above the respective pick
ups.
Test the Angle sector: we keep Vo and Io above the
respective pick ups.
Test the pick up of Io: we keep Vo above the pick up,
and the current angle at the measured Characteristic
Angle.
Test the pick up of
measured pick up, and the current angle at the
measured Characteristic Angle.
In this example we'll suppose we are testing a relay with the
characteristic displayed in the graph.
Rev. 1.34
 -90°; for other earth systems
o
Vo: we keep Io above the
Page 39 of 145
, the residual current
o

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents