  • Page 2: Table Of Contents

    Doc. SIE20167 Rev. 2 Page 3 of 11 INDEX 1 GENERAL DESCRIPTION _____________________________________________________________ 4 2 APPLICABLE STANDARDS ___________________________________________________________ 6 2.1 Electromagnetic Compatibility _______________________________________________________________ 6 2.2 Low voltage directive _______________________________________________________________________ 6 3 PERFORMANCE SUMMARY ___________________________________________________________ 7 3.1 Introduction ______________________________________________________________________________ 7 3.2 Specification ______________________________________________________________________________ 8 PowerMeterStore 1.877.766.5412 www.
  • Page 3: General Description

    This technical specification is to describe the technical characteristics of the battery test set BTS200 MKII, designed for the test of battery benches using the discharge method. This testing device can discharge the battery in different modes, to measure the capacity of new and used battery.
  • Page 4 Doc. SIE20167 Rev. 2 Page 5 of 11  In addition to the external clamp, the external burden current can now be measured also with a shunt.  If a test is interrupted, for instance because of a faulty contact or cell, after the repair it is possible to continue the test: this was not possible with the former device.
  • Page 5: Applicable Standards

    Doc. SIE20167 Rev. 2 Page 6 of 11 2 APPLICABLE STANDARDS The test set conforms to the EEC directives regarding Electromagnetic Compatibility and Low Voltage instruments. 2.1 Electromagnetic Compatibility Directive no. 2004/108/EC. Applicable Standard : EN61326-1 + A1 + A2. EMISSION - EN61000-3-2: harmonic content induced into the power supply: class A.
  • Page 6: Performance Summary

    The discharging current can be up to 130 A for voltages of 24 to 120 V DC nominal, and up to 70 A for 220 to 240 V. It is possible to use in parallel up to 10 BTS200 MKII, thus arriving up to 1300 A for voltages of 24 to 120 V DC nominal, and up to 700 A for 220 to 240 V.
  • Page 7: Specification

    Doc. SIE20167 Rev. 2 Page 8 of 11 3.2 Specification PARAMETER VALUE A) HARDWARE Maximum number of paralleling test sets 10: 1 master, 9 slave Absolute maximum battery voltage 270 V Minimum battery voltage 18 V Maximum power that can be discharged (one module) 16 kW Maximum power that can be discharged (10 modules) 160 kW...
  • Page 8 Doc. SIE20167 Rev. 2 Page 9 of 11 PARAMETER VALUE Operator interface Encoder with push-button Test start ON-OFF pushbutton Test stop from a remote contact Alarms 10-segments LED bar with current and alarms Test system LED Date and time Yes, with back-up battery PC communication USB 2.0 interface Paralleling interconnection...
  • Page 9 Doc. SIE20167 Rev. 2 Page 10 of 11 PERFORMANCE CHARACTERISTICS B) RESIDENT FIRMWARE Test settings Recorded in a NVM Number of memories Maximum test duration that can be recorded 15 h, with 15 s resolution Maximum test duration, not recorded in memory infinite Memory profile mode: maximum number of test steps 1 minute –...
  • Page 10 Accuracy: 1.5% up to 40 A; 2% up to 400 A. Maximum conductor diameter: 30 mm. ELU200 MKII Same as BTS200 MKII, without the local control PII21167 The following table lists a number of different types of batteries, the discharge current and the discharge power that can be programmed.