Functions
7.4 Device outputs (menu 4)
The address can only be changed if there is no cyclical communication and all acyclic
connections are closed.
Ident-Nr. (menu 4.1.2)
Selection of "Profile spec." or "Manufact. Spec." ident number, determines which GSD file will be
used.
Note
Correct Ident-Nr.
Select the correct "Ident-Nr." for the PROFIBUS communication in order to use the correct GSD
file.
Manufacturer specific: For use of 0x8159.gsd file (default setting)
Profile specific: For use of 0x9741.gsd file
min Tsdr (menu 4.1.3)
In this parameter the master on the PROFIBUS sets the minimum waiting time (minimum station
delay time of responder) which the SITRANS FUS060 PA slave has to observe before it answers
a master telegram (unit: bit time = 32 μs (time for 1 bit at 31.25 kbit/s)). This parameter is read-
only and has the default setting of 11 bits.
Digital outp 1 (menu 4.2)
(Terminals 5+ and 6-)
In this menu the output function (pulse, frequency or alarm/limits) is assigned and the signal
type as well as the pulse/frequency parameters are set.
Depending on the selected function (menu 4.2.1) either the pulse value and pulse width (menus
4.2.3 and 4.2.4) or the full scale frequency (menu 4.2.5) settings will affect the output.
The digital output 1 can indicate flow (pulse or frequency) and some alarms/limits.
60
SITRANS FUS060 with PROFIBUS PA
Operating Instructions, 09/2021, A5E02225054-AD