Siemens SITRANS FUS060 Operating Instructions Manual page 52

Ultrasonic flowmeters with profibus pa
Hide thumbs Also See for SITRANS FUS060:
Table of Contents

Advertisement

Functions
7.1 Display (menu 1)
On: At infrared key operation, the light turns on automatically and stays on for 1 hour after last
key action. Then it turns off.
Multi-Display (menu 1.1.6)
Shows the display with the settings done in menus 1.1.2, 1.1.3 and 1.1.4.
Flow (menu 1.2)
Shows the actual flow.
Totalizer (menu 1.3)
The actual totalizer readings are displayed with the correct sign, that is reverse totalizers with a
minus sign. The three totalizers are shown in submenus 1.3.1, 1.3.2 and 1.3.3.
Settings (all) (menu 1.3.4)
Reset+stop: All quantity totalizers are set to "0" and stopped. The totalizer for the error count
(menu 6.5.4) is set to "0" but not stopped.
Reset+start: All totalizers are set to "0" and started.
The totalizers can also be controlled individually (menus 3.4.3, 3.5.3 and 3.6.5).
Flow velocity (menu 1.4)
Actual average flow velocity in metering tube (in m/s)
Sound velocity (menu 1.5)
Actual sound velocity in medium (in m/s (default) or in ft/s)
Amplitude US (menu 1.6)
Relative ultrasonic amplitude of received ultrasonic signals (reference water) (in %)
Frequency and Current output (menus 1.7 and 1.8)
The arithmetically calculated output values are displayed in the menu 1.7 Frequency (in Hz) and
in menu 1.8 Current Output (in mA), irrespective of whether the output is used.
52
SITRANS FUS060 with PROFIBUS PA
Operating Instructions, 09/2021, A5E02225054-AD