06 Output terminal parameters

Parame
Parameter function
ter
06-00
MO1 output function selection
Control board relay function
06-01
selection (RA-RB-RC)
06-02
Reserved
06-03
Reserved
06-04
DFM (M) output function selection
DFM terminal output mode
06-05
selection
 indicates that the parameters can be set during operation
Setting range
0:No output
1:Inverter is running
2:Fault output (stop)
3:Frequency level detection FDT1 output
4:Frequency reached
5:Running at zero speed (no output when
stopped)
6:Motor overload pre-alarm
7:Inverter overload pre-alarm
8:Set count value reached
9:Designated count value reached
10:Length reached
11:PLC cycle completed
12:Cumulative running time arrived
13:Frequency limited
14:Torque limited
15:Ready for run
16:AVI1> AVI2 / ACI
17:Upper limit frequency reached
18:Lower limit frequency reached (operation
valid)
19:Undervoltage state output
20:Communication setting
21:(reserved)
22:(Reserved)
23:Zero speed running 2 (also output when
stopped)
24:Cumulative power-on time arrived
25:Frequency level detection FDT2 output
26:Frequency 1 reaches the output
27:Frequency 2 reaches the output
28:Current 1 reaches the output
29:Current 2 reaches the output
30:Timing reached
31:AVI1 input exceeds limit
32:Lost load
33:Reverse running
34:Zero current state
35:Module temperature reached
36:Output current exceeded
37:Lower limit frequency reached (also
output when stopped)
38:Warning output (continued)
39:reserved
40:Current running time reached
0:Pulse output (DFM (P))
1:Switch output (DFM (M))
44
Factory
setting
1
2
0
0