2.7.4
Block Diagram
2.8
WISE-4051
2.8.1
I/O Specification
Digital Input
–
Channel: 8
–
Logic level
–Dry Contact 0: Open
–Wet Contact 0: 0~3 V
–Channel 0~3 should be configured to dry contact or wet contact in the same
time
–Channel 4~7 should be configured to dry contact or wet contact in the same
time
–
Isolation: 3,000 V
–
Supports 32-bit Counter Input Function (Maximum signal frequency 3 kHz)
–
Keep/Discard Counter Value when Power-off
–
Supports Frequency Input Function (Maximum frequency 3 kHz)
–
Supports Inverted DI Status
RS-485 Port
–
Number of Ports: 1
–
Port Connector: 3.5mm spacing plug-in screw terminal block (shared with I/O
and power)
–
Baud Rate (bps): 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
–
Data Bits:7, 8
–
Stop Bits: 1, 2
–
Parity: None, Odd, Even
–
Flow Control: Auto flow control
–
Signals: DATA+ and DATA-
–
Protection: 15 kV ESD
–
Supported Protocol:
–Modbus/RTU (Total 32 address by max. 8 instructions)
Figure 2.26 WISE-4050 Block Diagram
1: Close to DI COM
or -3~0 V
DC
DC
1: 10~30 V
or -30~-10 V
DC
rms
29
(3 mA min.)
DC
WISE-4000 User Manual