HMS Networks Intesis User Manual page 11

Modbus server bacnet mstp and bacnet/ip client
Table of Contents

Advertisement

Modbus Server – BACnet Client
TM
Intesis
One of the following Modbus function codes can be used:
Function code
Byte Order
Register Address
The Modbus register address inside the slave device for the point.
Bit inside the
Bit inside the Modbus register (optional). The gateway allows bit decoding from
register
generic 16 bits input/holding Modbus registers.
Bit coding into 16 bits input/holding Modbus registers is used for some devices to
encode digital values into this type of registers, being these registers normally
accessible using Modbus function codes 3 and 4 (read holding/input registers).
Read/Write
0: Read
1: Write
2: Read / Write
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
16/32 bits Float.
16/ bits Bitfields.
Error comm
1- Read Coils.
2- Read Discrete Inputs.
3- Read Holding Registers.
4- Read Input Registers.
5- Write Single Coil.
6- Write Single Register.
15- Write Multiple Coils.
16- Write Multiple Registers.
Big Endian
Little Endian
Word Inverted Big Endian
Word Inverted Little Endian
User Manual r1.3 EN
URL
https://www.intesis.com
11 / 27

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Intesis and is the answer not in the manual?

Questions and answers

Table of Contents