Mounting Location - Endress+Hauser Cerabar PMC11 Operating Instructions Manual

Process pressure measurement
Hide thumbs Also See for Cerabar PMC11:
Table of Contents

Advertisement

Cerabar PMC11, PMC21, PMP11, PMP21, PMP23
Endress+Hauser
Type
Process isolating
diaphragm axis is
horizontal (A)
PMP11
Calibration position, no
PMP21
effect
PMP23
PMC11, PMC21
Calibration position, no
< 1 bar (15 psi)
effect
PMC11, PMC21
Calibration position, no
≥1 bar (15 psi)
effect
5.4

Mounting location

5.4.1
Pressure measurement
Pressure measurement in gases
Mount the device with shutoff device above the tapping point so that any condensate can
flow into the process.
1
Device
2
Shutoff device
Pressure measurement in vapors
For pressure measurement in vapors, use a siphon. The siphon reduces the temperature to
almost ambient temperature. Mount the device with a shutoff device at the same height as
the tapping point.
Advantage:
only minor/negligible heat effects on the device.
Note the max. permitted ambient temperature of the transmitter!
1
Device
2
Shutoff device
3
Siphon
Process isolating diaphragm
pointing upwards (B)
Up to +4 mbar (+0.058 psi)
Up to
+0.3 mbar (+0.0044 psi)
Up to +3 mbar (+0.0435 psi)
1
2
1
2
3
Installation
Process isolating diaphragm
pointing downwards (C)
Up to –4 mbar (–0.058 psi)
Up to
–0.3 mbar (–0.0044 psi)
Up to –3 mbar (–0.0435 psi)
A0021904
A0024395
17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cerabar pmc21Cerabar pmp11Cerabar pmp21Cerabar pmp23

Table of Contents