Connection Conditions; Connection Data - Endress+Hauser Cerabar PMC11 Operating Instructions Manual

Process pressure measurement
Hide thumbs Also See for Cerabar PMC11:
Table of Contents

Advertisement

Cerabar PMC11, PMC21, PMP11, PMP21, PMP23
Endress+Hauser
0 to 10 V output
Device
M12 plug
PMC11
0.5A
PMP11
2
1
3
6.1.2
Supply voltage
WARNING
L
Supply voltage might be connected!
Risk of explosion!
When using the measuring device in hazardous areas, installation must comply with
the corresponding national standards and regulations as well as the Safety Instructions.
All explosion protection data are given in separate documentation which is available
upon request. The Ex documentation is supplied as standard with all devices approved
for use in explosion hazardous areas.
Electronic version
4 to 20 mA output
0 to 10 V output
6.1.3
Current consumption and alarm signal
Number of wires
2
3
1)
For MAX alarm (factory setting)
6.2

Connection conditions

6.2.1
Cable specification
For valve plug: < 1.5 mm
2
6.3

Connection data

Valve plug
1
L+
3
2
L–
A0017576
Device
PMC11
PMP11
PMC21
PMP21
PMP23
PMC11
PMP11
Device
Normal operation
PMC11
≤ 26 mA
PMP11
PMC21
PMP21
PMP23
PMC11
< 12 mA
PMP11
(16 AWG) and Ø3.5 to 6.5 mm (0.14 to 0.26 in)
Electrical connection
4
L–
L+
0.5A
A0022822
Supply voltage
10 to 30 V DC
12 to 30 V DC
Alarm signal
> 21 mA
11 V
Cable
-
1)
21