BACnet
®
Gateway for VRF System

5.3.8 Batch_OperationMode_Setting (Multistate Output Object Type)

Property Identifier
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Device_Type
Status_Flags
Event_State
Reliability
Out_Of_Service
Number_Of_States
State_Text
Priority_Array
Relinquish_Default
Time_Delay
Notification_Class
Feedback_Value
Event_Enable
Acked_Transitions
Notify_Type
Event_Time_Stamps
Profile_Name
* Only available when specific object has a Notification Class configured
Operation Mode settings table
Mode commands can be set using the values in the following correspondence table.
Property Datatype
BACnetObjectIdentifier
CharacterString
BACnetObjectType
Unsigned
CharacterString
CharacterString
BACnetStatusFlags
BACnetEventState
BACnetReliability
BOOLEAN
Unsigned
BACnetArray[N] of
CharacterString
BACnetPriorityArray
Unsigned
Unsigned
Unsigned
Unsigned
BACnetEventTransitionBits
BACnetEventTransitionBits
BACnetNotifyType
BACnetArray[N] of
BACnetTimeStamp
CharacterString
Pesent_Value Contents displayed in State_Text
1
2
3
4
5
Copyright© 2010-2017 Fujitsu General Limited - All rights reserved
INSTRUCTION MANUAL r1.3.2 eng
Value
(Multistate Output, 0)
"Batch_OperationMode_Setting"
MULTISTATE_OUTPUT (14)
1 ~ 5
-
-
{FALSE, FALSE, FALSE, FALSE}
STATE_NORMAL (0)
NO_FAULT_DETECTED (0)
FALSE
5
Check Operation Mode settings below
BACnetPriorityArray
1
-
-
-
-
-
-
-
-
Cool
Heat
Fan
Dry
Auto
UTY-
ASHRAE
VBGX
R
R
R
R
R
R
W
W
O
-
O
-
R
R
R
R
O
R
R
R
R
R
O
R
R
R
R
R
O
R*
O
R*
O
W
O
R*
O
R*
O
R*
O
R*
O
-
30/103