Fujitsu BACnet UTY-VBGX Instruction Manual

Fujitsu BACnet UTY-VBGX Instruction Manual

Gateway for vrf system

Advertisement

Quick Links

BACnet
®
Gateway for VRF System
UTY-VBGX
INSTRUCTION MANUAL
Issue Date: 05/0217
r1.3.2 eng
PART No. 9708569239

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu BACnet UTY-VBGX

  • Page 1 BACnet ® Gateway for VRF System UTY-VBGX INSTRUCTION MANUAL Issue Date: 05/0217 r1.3.2 eng PART No. 9708569239...
  • Page 2 No part of this publication may be reproduced, stored in a retrieval system or transmitted in any form or any means electronic or mechanical, including photocopying and recording for any purpose other than the purchaser’s personal use without the written permission of Fujitsu General Limited.
  • Page 3 This “CONFIGURATION TOOL of BACnet ® GATEWAY for VRF SYSTEM” License Agreement (“LICENSE AGREEMENT”) is a legal agreement between you and Fujitsu General Limited (“FGL”) for the use of CONFIGURATION TOOL for VRF BACnet ® GATEWAY products consisting of computer software and online, electronic and/or printed documentation (collectively “SOFTWARE PRODUCT” or “SOFTWARE”).
  • Page 4 This LICENSE AGREEMENT shall be agreed based on the English language. The text in other language is made for reference purpose only and if there are any discrepancies between the English text and the text in other language, the English text shall prevail. 4/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 5 BACnet ® Gateway for VRF System INSTRUCTION MANUAL r1.3.2 eng Gateway for the integration of Fujitsu air conditioning systems in BACnet ® /IP enabled monitoring and control systems. Order Code: UTY-VBGX Model supporting up to 128 indoor units. 5/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 6: Table Of Contents

    Batch_Operation_Setting (Binary Output Object Type) ..............29 5.3.8 Batch_OperationMode_Setting (Multistate Output Object Type) ............30 5.3.9 Batch_FanSpeed_Setting (Multistate Output Object Type) ..............31 5.3.10 Batch_RC_Prohibition_Setting (Multistate Output Object Type) ............32 6/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 7 5.3.47 IU_rr_uu_RC_Prohibit_Setting (Multistate Output Object Type) ............70 5.3.48 OU_rr_uu_Error_Status (Binary Input Object Type) ................71 5.3.49 OU_rr_uu_ErrorCode_Status (Multistate Input Object Type) .............. 72 5.3.50 OU_rr_uu_ForcedOff_Status (Binary Input Object Type) ..............73 7/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 8 9 AC Unit Types compatibility ..........................98 10 Mechanical & electrical characteristics ....................... 98 11 Dimensions ................................. 99 12 Annex ................................100 Error codes ..............................100 RC Prohibition ............................103 8/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 9: Description

    BACnet ® Gateway for VRF System. The aim of this integration is to monitor and control your Fujitsu VRF air conditioning system, remotely, from your Control Center using any commercial SCADA or monitoring software that includes a BACnet ®...
  • Page 10: Functionality

    5000 Number of FGL control and status objects available into UTY-VBGX. The number of Indoor Units and Outdoor Units may vary on each project. These parameters can be configured through Configuration Tool (See section 8). 10/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 11: Protocol Implementation Conformance Statement

    MS/TP master (Clause 9), baud rate(s): MS/TP slave (Clause 9), baud rate(s): Point-To-Point, EIA 232 (Clause 10), baud rate(s): Point-To-Point, modem, (Clause 10), baud rate(s): LonTalk, (Clause 11), medium: _____ Other: 11/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 12: Device Address Binding

    ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS X 0208 Gateway If this product is a communication gateway, describe the types of non-BACnet equipment/network(s) that the gateway supports: Fujitsu VRF Air Conditioning Network. 12/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 13: Bacnet Interoperability Building Blocks Supported (Bibbs)

    Alarm and Event-Enrollment Summary-A GetEnrollmentSummary AE-ESUM-B Alarm and Event-Enrollment Summary-B GetEnrollmentSummary AE-INFO-A Alarm and Event-Information–A GetEventInformation AE-INFO-B Alarm and Event-Information–B GetEventInformation AE-LS-A Alarm and Event-LifeSafety–A LifeSafetyOperation AE-LS-B Alarm and Event-LifeSafety–B LifeSafetyOperation 13/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 14: Scheduling Bibbs

    Network Management - Connection NM-CE-B Establishment– B Disconnect-Connection-To- Network Who-Is-Router-To-Network I-Am-Router-To-Network I-Could-Be-Router-To- NM-RC-A Network Management - Router Configuration–A Network Initialize-Routing-Table Initialize-Routing-Table-ACK Who-Is-Router-To-Network I-Am-Router-To-Network NM-RC-B Network Management - Router Configuration–B Initialize-Routing-Table Initialize-Routing-Table-ACK 14/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 15: Device Management Bibbs

    Device Management - Object Creation and Deletion–A DeleteObject CreateObject DM-OCD-B Device Management - Object Creation and Deletion–B DeleteObject VT-Open DM-VT-A Device Management - Virtual Terminal–A VT-Close VT-Data VT-Open DM-VT-B Device Management - Virtual Terminal–B VT-Close VT-Data 15/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 16: Service Types

    ConfirmedPrivateTransfer Management ConfirmedTextMessage Services ReinitializeDevice VtOpen Virtual Terminal VtClose Services VtData Authenticate Security Services RequestKey I-Am I-Have UnconfirmedCOVNotification UnconfirmedEventNotification UnconfirmedPrivateTransfer UnconfirmedTextMessage Unconfirmed TimeSynchronization Services UtcTimeSynchronization Who-Has Who-Is LifeSafetyOperation SubscribeCOVProperty GetEventInformation 16/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 17: Objects

    IU_rr_uu_TempLimValid_Status OU_rr_uu_Error_Status OU_rr_uu_ForcedOff_Status Gateway_ES_Setting Batch_Operation_Setting IU_rr_uu_Operation_Setting Binary-Output IU_rr_uu_ThermostatOFF_Setting IU_rr_uu_Reset_Filter_Setting IU_rr_uu_TempLimValid_Setting OU_rr_uu_ForcedOff_Setting Binary-Value Calendar Command Device UTY-VBGX Event-Enrollment File Group Life-Safety-Point Life-Safety-Zone Loop Gateway_ErrorCode_Status IU_rr_uu_OperationMode_Status IU_rr_uu_FanSpeed_Status Multistate-Input IU_rr_uu_AirFlowDirVT_Status IU_rr_uu_AirFlowDirHZ_Status IU_rr_uu_RC_Prohibit_Status IU_rr_uu_ErrorCode_Status 17/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 18 BACnet ® Gateway for VRF System INSTRUCTION MANUAL r1.3.2 eng OU_rr_uu_ErrorCode_Status OU_rr_uu_CapacitySave_Status OU_rr_uu_LowNoiseOp_Status Batch_OperationMode_Setting Batch_FanSpeed_Setting Batch_RC_Prohibition_Setting IU_rr_uu_OperationMode_Setting IU_rr_uu_FanSpeed_Setting Multistate-Output IU_rr_uu_AirFlowDirVT_Setting IU_rr_uu_AirFlowDirHZ_Setting IU_rr_uu_RC_Prohibit_Setting OU_rr_uu_LowNoiseOp_Setting OU_rr_uu_CapacitySave_Setting Multistate-Value Notification-Class NotificationClass_x Program Schedule Trend-Log 18/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 19: Member Objects

    IU_rr_uu_HeatTempLoLim_Setting 15rruu IU_rr_uu_HeatTempHiLim_Setting 16rruu IU_rr_uu_Exists_Status 10rruu IU_rr_uu_Operation_Status 11rruu IU_rr_uu_ThermostatOFF_Status 12rruu IU_rr_uu_FilterSign_Status 13rruu IU_rr_uu_Emergency_Status 14rruu IU_rr_uu_Error_Status 15rruu IU_rr_uu_TempLimValid_Status 16rruu IU_rr_uu_Operation_Setting 10rruu IU_rr_uu_ThermostatOFF_Setting 11rruu IU_rr_uu_Reset_Filter_Setting 12rruu IU_rr_uu_TempLimValid_Setting 13rruu IU_rr_uu_OperationMode_Status 10rruu IU_rr_uu_FanSpeed_Status 11rruu 19/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 20: Type: Outdoor Unit

    Multistate Outputs and Multistate Values, it cannot be read the whole array at once, so “Array Index” must be specified in order to obtain the text of the corresponding state. 20/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 21 2.All control signals such as Operation Mode Setting, Temperature Setting and FAN Speed Setting are accepted when indoor unit is “ON”. 21/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 22: Fujitsu Ac Gateway (Device Object Type)

    Current time UTC_Offset INTEGER Daylight_Savings_Status BOOLEAN APDU_Segment_Timeout Unsigned 3000 APDU_Timeout Unsigned 3000 Number_of_APDU_ Unsigned Retries List_Of_Session_Keys List of BACnetSessionKey - Time_Synchronization_ List of BACnetRecipient Recipients List of Device_Address_Binding NULL (empty) BACnetAddressBinding 22/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 23 BACnetArray[N] of Auto_Slave_Discovery BOOLEAN Slave_Address_Binding BACnetAddressBinding Last_Restart_Reason BACnetRestartReason Time_Of_Device_Restart BACnetTimeStamp Restart_Notification_ List of BACnetRecipient Recipients UTC_Time_ Synchronization_ List of BACnetRecipient Recipients Time_Synchronization_ Unsigned Interval Align_Intervals BOOLEAN Interval_Offset Unsigned Profile_Name CharacterString 23/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 24: Gateway_Es_Status (Binary Input Object Type)

    BACnetDatetime Time_Delay Unsigned Notification_Class Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 24/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 25: Gateway_Es_Setting (Binary Output Object Type)

    INACTIVE (0) Time_Delay Unsigned Notification_Class Unsigned Feedback_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 25/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 26: Gateway_Error_Status (Binary Input Object Type)

    BACnetDatetime Time_Delay Unsigned Notification_Class Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 26/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 27: Gateway_Errorcode_Status (Multistate Input Object Type)

    * Only available when specific object has a Notification Class configured Gateway Error Code table Gateway Error Code can be interpreted using the values in the following correspondence table. Pesent_Value Description No Error Hardware Error No Configuration Present 27/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 28: Batch_Settemp_Setting (Analog Output Object Type)

    REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 28/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 29: Batch_Operation_Setting (Binary Output Object Type)

    INACTIVE (0) Time_Delay Unsigned Notification_Class Unsigned Feedback_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 29/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 30: Batch_Operationmode_Setting (Multistate Output Object Type)

    * Only available when specific object has a Notification Class configured Operation Mode settings table Mode commands can be set using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Cool Heat Auto 30/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 31: Batch_Fanspeed_Setting (Multistate Output Object Type)

    Fan Speed settings table Fan Speed commands can be set using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Pesent_Value Contents displayed in State_Text Quiet Med-Low High Med-High Auto 31/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 32: Batch_Rc_Prohibition_Setting (Multistate Output Object Type)

    Unsigned Time_Delay Unsigned Notification_Class Unsigned Feedback_Value Unsigned Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 32/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 33 REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 33/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 34 REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 34/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 35 REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 35/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 36 REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 36/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 37 REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 37/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 38 REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 38/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 39 REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 39/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 40 REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured. 40/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 41 REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 41/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 42 10.5 18.5 11.5 19.5 12.5 20.5 13.5 21.5 14.5 22.5 15.5 23.5 16.5 24.5 17.5 25.5 26.5 27.5 28.5 29.5 42/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 43 REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 43/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 44 REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 44/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 45 REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured. 45/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 46 REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 46/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 47 REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 47/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 48 REAL Low_Limit REAL Deadband REAL Limit_Enable BACnetLimitEnable Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 48/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 49 BACnetDatetime Time_Delay Unsigned Notification_Class Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 49/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 50 BACnetDatetime Time_Delay Unsigned Notification_Class Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 50/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 51 BACnetDatetime Time_Delay Unsigned Notification_Class Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 51/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 52 BACnetDatetime Time_Delay Unsigned Notification_Class Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 52/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 53 BACnetDatetime Time_Delay Unsigned Notification_Class Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 53/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 54 BACnetDatetime Time_Delay Unsigned Notification_Class Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 54/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 55 BACnetDatetime Time_Delay Unsigned Notification_Class Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 55/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 56 INACTIVE (0) Time_Delay Unsigned Notification_Class Unsigned Feedback_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 56/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 57 INACTIVE (0) Time_Delay Unsigned Notification_Class Unsigned Feedback_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 57/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 58 INACTIVE (0) Time_Delay Unsigned Notification_Class Unsigned Feedback_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 58/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 59 INACTIVE (0) Time_Delay Unsigned Notification_Class Unsigned Feedback_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 59/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 60 * Only available when specific object has a Notification Class configured Operation Mode status table Mode status can be read using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Cool Heat Auto 60/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 61 Fan Speed status table Fan speed status can be read using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Pesent_Value Contents displayed in State_Text Quiet High Med-Low Med-High Auto 61/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 62 * Only available when specific object has a Notification Class configured Air Flow Dir VT status table Vertial Air Flow direction status can be red using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Swing 62/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 63 * Only available when specific object has a Notification Class configured Air Flow Dir HZ status table Horizontal Air Flow Direction status can be read using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Swing 63/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 64 List of Unsigned Fault_Values List of Unsigned Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 64/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 65 * Only available when specific object has a Notification Class configured NOTE: For the error content, refer to the “Error content table” using the Present_Value of the appropriate series. Error contents may be added without prior notice. 65/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 66 * Only available when specific object has a Notification Class configured Operation Mode settings table Mode commands can be set using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Cool Heat Auto 66/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 67 Fan Speed settings table Fan speed commands can be set using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Pesent_Value Contents displayed in State_Text Quiet High Med-Low Med-High Auto 67/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 68 * Only available when specific object has a Notification Class configured Air Flow Dir VT settings table Vertial Air Flow Direction commands can be set using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Swing 68/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 69 * Only available when specific object has a Notification Class configured Air Flow Dir HZ settings table Horizontal Air Flow Direction commands can be set using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Swing 69/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 70 Unsigned Notification_Class Unsigned Alarm_Values Unsigned Fault_Values Unsigned Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 70/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 71 BACnetDatetime Time_Delay Unsigned Notification_Class Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 71/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 72 BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured You can check the error codes for each AC system on section Error codes (section 12.1) 72/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 73 BACnetDatetime Time_Delay Unsigned Notification_Class Unsigned Alarm_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured 73/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 74 Capacity Save status table Capacity Save status can be read using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Pesent_Value Contents displayed in State_Text Not set 100% 74/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 75 Capacity Save setting table Capacity Save can be set using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Pesent_Value Contents displayed in State_Text Not set 100% 75/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 76 INACTIVE (0) Time_Delay Unsigned Notification_Class Unsigned Feedback_Value BACnetBinaryPV Event_Enable BACnetEventTransitionBits Acked_Transitions BACnetEventTransitionBits Notify_Type BACnetNotifyType BACnetArray[N] of Event_Time_Stamps BACnetTimeStamp Profile_Name CharacterString * Only available when specific object has a Notification Class configured. 76/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 77 Low Noise Operation Status can be checked using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Pesent_Value Contents displayed in State_Text 2/-/- Not Set -/-/E 2/-/E 2/A/- -/A/- 2/A/E -/A/E 3/-/- 1/-/- 3/-/E 1/-/E 3/A/- 1/A/- 3/A/E 1/A/E 77/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 78 E:Simultaneously controlled through external input of outdoor unit. If this value is set, the actual low noise operation will also depend on the external input signal connected to the outdoor unit. 78/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 79 Low Noise Operating commands can be set using the values in the following correspondence table. Pesent_Value Contents displayed in State_Text Pesent_Value Contents displayed in State_Text Stop Level2-Ability Level3-Quiet Level1-Quiet Level3-Ability Level1-Ability Level2-Quiet 79/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 80 VBGX Object_Identifier BACnetObjectIdentifier (Notification_Class, 15) Object_Name CharacterString "NotificationClass_0" ~ "NotificationClass_9" Object_Type BACnetObjectType NOTIFICATION_CLASS (15) Description CharacterString Notification_Class Unsigned Priority BACnetARRAY[3] of Unsigned Ack_Required BACnetEventTransitionBits Recipient_List BACnetLIST of BACnetDestination Profile_Name CharacterString 80/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 81 Install a leakage circuit breaker to power supply cable in accordance with the related laws and regulations and electric company standards. Use a power source exclusively for this unit. Never share the power source with other electrical equipment. Doing so will cause fire and electric shock. 81/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 82 Power cable wire length Tie cable here 8 mm Ethernet Power Supply NOTE: Earth (E) wire shall be 8mm longer than L (Line) and N (Neutral) wires. Figure 6.1 Gateway connections 82/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 83 Install the transmission cables securely to the terminal block. Confirm that external force is not applied to the cable. Use transmission cables made of the specified cable. If intermediate connection or insertion fix- ing are imperfect, it will cause electric shock, fire, etc. 83/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 84 (7) Do not fix 2 or more power supply cables with 1 screw/terminal. WARNING Apply an appropriate tightening torques for the terminal screw. Otherwise, abnormal overheating may occur and possibly cause heavy damage inside the unit,. 84/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 85 Use the LON connector in the left bottom corner of the gateway in order to connect the VRF network to the UTY- VBGX. Remember to follow all safety precautions indicated by Fujitsu. Modifying some other parameters can affect proper communication.
  • Page 86 Ethernet: Using the ETH port of the gateway. How to check connectivity is explained in section 6.3. • USB cable: To connect the device to the PC the USB cable supplied should be plugged to the USB Console port. 86/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 87 10. Open the Fujitsu Communication Viewer window and check that there is communication activity, some RX frames. This means that the communication with the VRF network is OK. In case of no communication activity, check that the VRF network is operative and well configured and check also the communication cable used to connect both systems.
  • Page 88 Service led of LON port. LED_8 (green) Device has IP address (after DHCP or manually assigned). Button Description PUSH_A Sends I-Am msg on bacnet-ip side. PUSH_B Service pin of LON port. 88/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 89 Welcome screen From the welcome screen, access is granted to: the Fujitsu General Limited Website, start a new project, load a previous project from our computer or get the current project running on the gateway.
  • Page 90 If installing more than one BACnet ® Gatewy for VRF System, connect them one by one and assign an IP to each of them in case DHCP is not available. 90/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 91 6. Gateway: Enter the router or default gateway address if needed. In case you don’t want to use it, leave it blank. 7. Password: Enter the access password to allow IP connection to the box (admin by default). 91/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 92 6. Network Role: Select the gateway role from a BACnet network device point of view: a. Disabled b. Foreign device c. BBMD 7. Show advanced configuration: Enables Notification Classes configuration. Figure 8.6 Notification Class configuration 92/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 93 Use this function to scan the VRF network automatically to look for the current units connected to the system. Note: Scan may take from 5 to 6 minutes depending on each installation specs. 93/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 94 2. Active: Indicates if the signal is currently active for this configuration. If not, it will not be considered by the tool when downloading it to the gateway. 3. Object BACnet name: Signal's descriptive name that identifies the signal. 4. BACnet type: Type of BACnet object. 94/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 95 Export: Exports the current configuration. Only Excel format is supported. d) Check table: Checks the current configuration to make sure Receive/Send Send or receive the current configuration of the gateway. Figure 8.11 Send and receive options 95/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 96 Diagnostic Use this setting to check the current communication status of the gateway on both: BACnet and FGL. Communication with the box, the BACnet side and the Fujitsu system can be check using the viewer available. Figure 8.12 Diagnostic tool 1.
  • Page 97 Check the current signal values on both: BACnet and VRF network side (connection to the VRF network and/or BACnet client is required). The Signals Viewer can be used even though only one system is connected to the gateway, BACnet or Fujitsu AC. Therefore, it becomes convenient for supervision and testing the system.
  • Page 98 1 x Power 1 x Error Operational 0°C to +46°C temperature Operational 5% to 95%, non-condensing humidity Preservation -10°C to +60°C Temperature Protection IP20 (IEC60529). RoHS conformity Compliant with RoHS directive (2002/95/CE). 98/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 99 BACnet ® Gateway for VRF System INSTRUCTION MANUAL r1.3.2 eng 11 Dimensions [mm] 99/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 100 ® Gateway for VRF System INSTRUCTION MANUAL r1.3.2 eng 12 Annex Error codes Below you can find a list of error codes from Fujitsu air conditioning system. V-II/J-II/VR-II Series Present_Value Error Code Error Description Serial communication error between indoor/outdoor units...
  • Page 101 Outdoor unit pressure error 2 Outdoor unit heat exchanger temperature error Suction temperature abnormal Poor refrigerant circulation Current overload error Outdoor unit special operation error Ambient temperature error Out of the possible operation range 101/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 102 System tool interface error System tool environment error RB unit error Branch boxes error Total heat exchanging, ventilation unit error Domestic hot water unit error Zone control interface error DX-Kit error 102/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...
  • Page 103 -/TR/TP/MD/-/-/- -/-/TP/MD/-/-/- -/TR/TP/MD/-/-/FL -/-/TP/MD/-/-/FL -/TR/TP/MD/-/ON/- -/-/TP/MD/-/ON/- -/TR/TP/MD/-/ON/FL -/-/TP/MD/-/ON/FL -/TR/TP/MD/OP/-/- -/-/TP/MD/OP/-/- -/TR/TP/MD/OP/-/FL -/-/TP/MD/OP/-/FL -/TR/TP/MD/OP/ON/- -/-/TP/MD/OP/ON/- -/TR/TP/MD/OP/ON/FL -/-/TP/MD/OP/ON/FL ALL/-/-/-/-/-/- -/TR/-/-/-/-/- Note: “ON” and “OP” may not be set at the same time. 103/103 Copyright© 2010-2017 Fujitsu General Limited - All rights reserved...

Table of Contents