Gateway_Es_Status (Binary Input Object Type) - Fujitsu BACnet UTY-VBGX Instruction Manual

Gateway for vrf system
Table of Contents

Advertisement

BACnet
®
Gateway for VRF System

5.3.2 Gateway_ES_Status (Binary Input Object Type)

The current Energy Saving status can be monitored.
Property Identifier
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Device_Type
Status_Flags
Event_State
Reliability
Out_Of_Service
Polarity
Inactive_Text
Active_Text
Change_Of_State_Time
Change_Of_State_Count
Time_Of_State_Count_Reset
Elapsed_Active_Time
Time_Of_Active_Time_Reset
Time_Delay
Notification_Class
Alarm_Value
Event_Enable
Acked_Transitions
Notify_Type
Event_Time_Stamps
Profile_Name
* Only available when specific object has a Notification Class configured
Property Datatype
BACnetObjectIdentifier
CharacterString
BACnetObjectType
BACnetBinaryPV
CharacterString
CharacterString
BACnetStatusFlags
BACnetEventState
BACnetReliability
BOOLEAN
BACnetPolarity
CharacterString
CharacterString
BACnetDatetime
Unsigned
BACnetDatetime
Unsigned
BACnetDatetime
Unsigned
Unsigned
BACnetBinaryPV
BACnetEventTransitionBits
BACnetEventTransitionBits
BACnetNotifyType
BACnetArray[N] of
BACnetTimeStamp
CharacterString
Copyright© 2010-2017 Fujitsu General Limited - All rights reserved
INSTRUCTION MANUAL r1.3.2 eng
Value
(Binary Input, 0)
"Gateway_ES_Status"
BINARY_INPUT (3)
INACTIVE (0) / ACTIVE (1)
-
-
{FALSE, FALSE/TRUE, FALSE, FALSE}
STATE_NORMAL (0)
NO_FAULT_DETECTED (0),
UNRELIABLE_OTHER (7)
FALSE
NORMAL (0)
"Not used"
"Energy Saving"
-
-
-
-
-
-
-
-
-
-
-
-
-
UTY-
ASHRAE
VBGX
R
R
R
R
R
R
R
R
O
-
O
-
R
R
R
R
O
R
R
R
R
R
O
R
O
R
O
R
O
R
O
R
O
R
O
R
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
-
24/103