NOTE: Mount the device in a vertical position and ensure proper space for all connectors when mounted. Product is
to be connected only to Ethernet and LON networks without routing to the outside plant and connect to outdoor
devices through SELV ports.
Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according to the instructions.
IMPORTANT: Tie the power supply and the LON cable to the corresponding tie fixture as shown in Figure 6.1.
When doing so, cable must be tied thru only one of the 2 holes of the tie fixture. If cable is tied thru both of the 2
holes of the tie fixture, the cable may become loose and can be dangerous.
Power Supply
Connect mains to the power supply connector as:
1.- Brown: Line (L)
2.- Yellow: Earth / Ground (E)
3.- Blue: Neutral (N)
A readily accessible disconnect device shall be incorporated in the building installation wiring.
Ethernet / BACnet IP (UDP) / Console (UDP & TCP)
Connect the cable coming from the IP network to the connector ETH of the gateway. Use an Ethernet CAT5 cable.
VRF Network
Connect the LON bus to connectors A3 (+), A4 (-) and A1/A2 (SNGD) of gateway's PCB. There are no polarities for
the A3 (+), A4 (-) signals.
Console Port
Connect a mini-type B USB cable from your computer to the gateway to allow communication between the
Configuration Software and the gateway. Remember that Ethernet connection is also allowed for configuration.
Wiring Requirements & Notes
6.2.1 Electrical Requirement
Use
Maximum
Power supply
cable
Minimum
Transmission
0.33 mm
cable
Ethernet cable
Fuse capacity
1.25 A
Before starting installation work, turn off the power of this unit and the connection destination. Do not turn on the power again
until installation is completed. Otherwise, it will cause electric shock or fire.
Use specified cables or accessory cables to connect to this unit.
Do not modify the cables to connect this unit other than those specified, do not use extension cables, and do not use
independent branch wiring. It may cause electric shock or fire.
Install the transmission cables securely to the terminal block. Confirm that external force is not applied to the cable. Use
transmission cables made of the specified cable. If intermediate connection or insertion fix- ing are imperfect, it will cause
electric shock, fire, etc.
Size
1.25 mm
2
(16AWG)
0.5 mm
2
(20AWG)
2
(22AWG)
Copyright© 2010-2017 Fujitsu General Limited - All rights reserved
CAUTION
Wire type
Type 60245 IEC
57 or equivalent
22AWG LEVEL4 (NEMA) nonpolar
2 core, twisted pair solid core
Shielded
Category 5 or Higher STP cable
with RJ45 connector
WARNING
INSTRUCTION MANUAL r1.3.2 eng
Remarks
1Ø AC208–240 V 50/60Hz, 2
Cable + earth (ground) [Always
earth (ground) the unit]
LONWORKS
®
compatible
cable
Ethernet cable