Batch_Operationmode_Setting (Multistate Output Object Type) - Fujitsu UTY-VBGX Instruction Manual

Bacnet gateway for vrf system
Table of Contents

Advertisement

BACnet Gateway for VRF System

5.3.8 Batch_OperationMode_Setting (Multistate Output Object Type)

Property Identifier
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Device_Type
Status_Flags
Event_State
Reliability
Out_Of_Service
Number_Of_States
State_Text
Priority_Array
Relinquish_Default
Time_Delay
Notification_Class
Feedback_Value
Event_Enable
Acked_Transitions
Notify_Type
Event_Time_Stamps
Event_Message_Texts
Event_Message_Texts_Config
Event_Detection_Enable
Event_Algorithm_Inhibit_Ref
Event_Algorithm_Inhibit
Time_Delay_Normal
Reliability_Evaluation_Inhibit
Property_List
Profile_Name
* Only available when specific object has a Notification Class configured
Property Datatype
BACnetObjectIdentifier
CharacterString
BACnetObjectType
Unsigned
CharacterString
CharacterString
BACnetStatusFlags
BACnetEventState
BACnetReliability
BOOLEAN
Unsigned
BACnetArray[N] of
CharacterString
BACnetPriorityArray
Unsigned
Unsigned
Unsigned
Unsigned
BACnetEventTransitionBits
BACnetEventTransitionBits
BACnetNotifyType
BACnetArray[N] of
BACnetTimeStamp
BACnetArray[3] of
CharacterString
BACnetArray[3] of
CharacterString
BOOLEAN
BACnetObjectPropertyRefer
ence
BOOLEAN
Unsigned
BOOLEAN
BACnetArray[N] of
BACnetPropertyIdentifier
CharacterString
Copyright© 2021 Fujitsu General Limited - All rights reserved
INSTRUCTION MANUAL r1.4.0 eng
Value
(Multistate Output, 0)
"Batch_OperationMode_Setting"
MULTISTATE_OUTPUT (14)
1 ~ 5
-
-
{FALSE, FALSE, FALSE, FALSE}
STATE_NORMAL (0)
NO_FAULT_DETECTED (0)
FALSE
5
Check Operation Mode settings below
BACnetPriorityArray
1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
BACnetArray[N]
-
UTY-
ASHRAE
VBGX
R
R
R
R
R
R
W
W
O
-
O
-
R
R
R
R
O
R
R
R
R
R
O
R
R
R
R
R
O
R*
O
R*
O
W
O
R*
O
R*
O
R*
O
R*
O
-
O
-
O
R*
O
-
O
-
O
-
O
-
R
R
O
-
39/159